Honeywell Sensepoint XCD RFD Technical Manual page 41

Remote flammable detector
Hide thumbs Also See for Sensepoint XCD RFD:
Table of Contents

Advertisement

Sensepoint XCD RFD Technical Manual
PEAK READING
DISPLAYED WITH OUTPUT
INHIBITED '
bumP
PEAK STRING FLASHING.
tESt
APPLY BUMP TEST
GAS AND CHECK PEAK
READING ON DISPLAY.
'Forc' DISPLAYED WITH '
' ICON. DEFAULT FORCE
Forc
CURRENT '4.00' FLASHES.
Curr
USE  TO CHANGE TO
REQUIRED mA LEVEL.
'AL1', ICON DISPLAYED
AND CURRENT ALARM
SEt
LEVEL 1 CONCENTRATION
ALrm
FLASHES. USE  TO
CHANGE TO REQUIRED
CONCENTRATION LEVEL.
'rL1' DISPLAYED AND
'AL1', 'AL2', 'Inht' or 'FLt'
Set
FLASHES. USE  TO
rLY
CHANGE TO REQUIRED
RELAY TARGET.
'rL3' DISPLAYED AND
'AL1', 'AL2', 'Inht' or 'FLt'
FLASHES. USE  TO
CHANGE TO REQUIRED
RELAY TARGET.
'rLY', 'ON' DISPLAYED AND
CURRENT RELAY-ON TIME
rlY
FLASHES. USE  TO
OPr
CHANGE TO REQUIRED
RELAY-ON DELAY.
'Loc' DISPLAYED WITH
FIRST 4 CHARACTERS OF
THE LOCATION STRING.
USE  TO CHANGE THE
1ST CHARACTER OF
Set
CURRENT LOCATION
Loc
STRING. USE  TO MOVE
TO NEXT CHARACTER
AND SET REST OF
STRING. MAXIMUM 12
CHARACTERS CAN BE
SET.
'tEmP' DISPLAYED WITH
'°C' OR '°F' FLASHING.
tEm
USE  TO CHANGE TO
PUnIt
REQUIRED TEMPERATURE
UNIT.
'Forc' DISPLAYED and 'AL1'
FLASHING TO SELECT
tES
TEST-REQURED ALARM.
tALrm
USE '' TO FORCE
ALARM1.
QUITS MENU MODE AND
9uIt
RETURNS TO MONITORING
MODE
OK


1
Refer to section 10.1 for detailed zero and span calibration procedures. Re-calibrate the detector if left un-powered for
periods in excess of 24 hours.
2
The calibration due warning counter is automatically reset after a successful calibration.
CURRENT GAS
CONCENTRATION
' ICON AND
DISPLAYED WITH
OUTPUT INHIBITED '
ICON FLASHING.
UNIT TRANSMITS THE
CURRENT
IF YOU WANT TO EXIT
FROM THIS MENU, USE
ABORT FUNCTION
'AL1' DISPLAYED WITH
'NonE', 'rISE' OR 'FALL'
FLASHING. USE 
TO SELECT REQUIRED
ALARM ACTION.
'rL1' DISPLAYED
AND 'dEEn' or 'Enr9'
FLASHES. USE  TO
CHANGE TO REQUIRED
RELAY ACTION.
'rL3' DISPLAYED
AND 'dEEn' or 'Enr9'
FLASHES. USE  TO
CHANGE TO REQUIRED
RELAY ACTION.
'rLY', 'OFF' DISPLAYED
AND CURRENT RELAY-
OFF TIME FLASHES.
USE  TO CHANGE
TO REQUIRED RELAY-
OFF DELAY.
'Loc' DISPLAYED NEW
LOCATION STRING. THE
STRING MOVES RIGHT-
TO-LEFT TO SHOW
WHOLE CHARACTERS
TWICE. THEN UNIT
AUTOMATICALLY
RETURNS TO MENU
MODE.
UNIT RETURNS TO
MENU MODE
GAS NAME, CURRENT
GAS CONCENTRATION
DISPLAYED AND '
' ICON AND AL ICON
FLASH.
OK

Table 12. Configuration Mode Operation
SPXCDHMRFENU Issue 1
UNIT RETURNS TO
'
MENU MODE
'AL2', ICON
DISPLAYED
AND CURRENT
ALARM LEVEL 2
CONCENTRATION
FLASHES. USE
 TO CHANGE
TO REQUIRED
CONCENTRATION
LEVEL.
'Rl2' DISPLAYED AND
'AL1', 'AL2', 'Inht' or
'FLt' FLASHES. USE
 TO CHANGE TO
REQUIRED RELAY
TARGET.
UNIT RETURNS TO
MENU MODE
'Ltch' DISPLAYED
AND 'YES' or 'No'
FLASHES. USE 
TO CHANGE TO
REQUIRED LATCH
OPTION.
UNIT RETURNS TO
MENU MODE
OK

41
'AL2' DISPLAYED WITH
'NonE', 'rISE' OR 'FALL'
FLASHING. USE 
TO SELECT REQUIRED
ALARM ACTION AND USE
'' TO RETURN TO MENU
MODE.
'rL2' DISPLAYED AND
'dEEn' or 'Encr9' FLASHES.
USE  TO CHANGE
TO REQUIRED RELAY
ACTION.
UNIT RETURNS TO MENU
MODE
OK
