Programming
In systems that implement multiple network audio sources, the priority of the network sources will be determined by the priority
assigned to the active input on the network source. For example, a DVC that is sending an ACU Local Paging Level 1 of priority 1 to a
network DVC will take priority over a DVC that is sending an ACU Local Paging level 2 of priority 7 to the same DVC. In the event of
the priority levels being identical for multiple network audio sources, the first source to activate will be granted priority.
ONYXWorks Workstation
1.
Set the workstation to FCC Mode.
2.
Create MN audio paging group(s).
3.
Set up the workstation priorities for an MN CCS station. In Figure 3.10, Inputs are shown in their fixed order, which comply with
UL2572. CCS Inputs are:
• 5 (CCS Local Paging Level 1)
• 11 (CCS Local Paging Level 2)
• 13 (Local General Paging)
3.3.4 MN Mapping
MN Mapping determines if a ZF20 MN alarm will suppress fire events at the panel if there is an active MN alarm at another node and
MN is the highest priority.
NFS2-3030 in Network Display Mode
MN network mapping may be done at the panel or in Veri-
Fire Tools.
Panel: Navigate to the Panel Program Menu 1 screen. Press
the softkey next to NETWORK MAPPING to bring up the
screen shown in Figure 3.11. The panel will monitor the
nodes mapped here for MN alarm messages in order to sup-
press fire.
VeriFire Tools: In the Network Mapping branch of VeriFire Tools, select the nodes in the Mass Notification column that the panel will
monitor for MN alarm messages in order to suppress fire.
NCA-2
NCA-2 Network event mapping defines its MN mapping; there is no unique MN mapping for the NCA-2.
Mass Notification — P/N LS10063-000NF-E:E 06/26/2019
0 0 1 : O F F L I N E /
0 0 3 : O N L I N E
0 0 5 : O F F L I N E /
0 0 7 : O F F L I N E /
0 0 9 : O N L I N E
0 1 2 : O F F L I N E /
0 1 3 : O F F L I N E /
0 1 5 : O F F L I N E /
A U T O P R O G R A M
N E X T
Figure 3.11 Network Mapping Screen, NFS2-3030
Figure 3.12 MN Mapping, NFS2-3030
N E T W O R K M A P P I N G
S C R E E N 1 o f 1 5
0 0 2 : O F F L I N E /
/ M A P P E D
0 0 4 : O F F L I N E /
0 0 6 : O F F L I N E /
0 0 8 : O F F L I N E /
/ M A P P E D
0 1 0 : O F F L I N E /
0 1 2 : O F F L I N E /
0 1 4 : O F F L I N E /
0 1 6 : O F F L I N E /
A C C E P T
Check boxes for
the nodes to be
monitored for MN
events (a
maximum of four
DVCs and one fire
panel). The
NFS2-3030 node
being
programmed is
grayed out and
unavailable.
Programming
B A C K