Monitor module

Advertisement

FIGURE 3. TYPICAL 2-WIRE INITIATING CIRCUIT CONFIGURATION, NFPA CLASS D OR SECURITY SYSTEMS
NOTE: For UL Listed security installations, the FMM-1 must be mounted within the control panel enclosure.
ANY NUMBER OF UL LISTED CONTACT
CLOSURE DEVICES MAY BE USED. DO NOT MIX
FIRE ALARM INTIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.
47K EOL
RESISTOR
ELR-47K
INITIATING DEVICE CIRCUIT (IDC) - NFPA CLASS B
POWER LIMITED: 450µA MAX. @ 11 VDC MAX
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
FIGURE 4. TYPICAL 4-WIRE FAULT TOLERANT INITIATING CIRCUIT CONFIGURATION, NFPA CLASS A
ANY NUMBER OF UL LISTED CONTACT
CLOSURE DEVICES MAY BE USED. DO NOT MIX
FIRE ALARM INTIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.
EOL RESISTOR IS
INTERNAL AT
TERMINALS 8 & 9
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
UL 2610 REQUIREMENTS
This product is intended to be installed in accordance with the following:
• NFPA 70 - National Electric Code
• UL 681 - Standard for Installation and Classifcation of Burglar and
Holdup Alarm Systems
• UL827 - Standard for Central Station Alarm Services
See panel installation document for specifications on wire sizes to use with
this module.
See relevant control panel for additional information on programming, testing
and maintenance. Testing should be performed annually, as per NFPA72.
The installer should be familiar with and follow the best practices set forth
within ANSI/SIA CP-01 for troubleshooting and reduction in dispatch calls.
NOTIFIER
®
and Honeywell
®
are registered trademarks of Honeywell International, Inc.
TO NEXT
DEVICE
MONITOR
MODULE
TO NEXT
DEVICE
MONITOR
MODULE
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
2
PREVIOUS DEVICE
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMENDED
CONNECT MODULES TO LISTED COMPATIBLE
NOTIFIER CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
SHIELDED-TWISTED PAIR
IS RECOMENDED