Honeywell GAMEWELL LCD-SLP Product Installation Document page 13

Liquid crystal display-smart loop panel
Table of Contents

Advertisement

Section 4: LCD-SLP Display Panel
4.1 LCD-SLP Touchscreen LEDs and Switches
Figure 4.1.1 illustrates the screen that appears when you program in CAMWorks for Non-Releasing Fire applications.
.
Figure 4.1.1 LCD-SLP Non-Releasing Fire Touchscreen LEDs and Switches
Table 4.1.1 lists the LCD-SLP, LED indicators, Audible/Visual Status indicators and the switches.
Designation
Description
AC Power
GREEN
Fire Alarm
RED
Hazard
BLUE
Supervisory
YELLOW
Trouble
YELLOW
Silenced
YELLOW
Condition
Alarm
Hazard
Supervisory
Trouble
Switch
Menu
Drill
Reset
User-Defined Switches
Note 1: The Menu, Drill and User-Defined switches are not available on Releasing displays.
Note 2: The Menu and Drill switches are not available when the Releasing Zone to which the LCD-SLP belongs is
OFF-NORMAL.
Table 4.1.1 LCD-SLP LED Indicators, Audible/Visual Indicators and Switches
LCD-SLP Product Installation Document — P/N LS10045-000GF-E:E 12/16/2019
FIR E A LA R M H A ZA R D SU PE R V IS O R Y TR O U B LE
A C P O W E R
M ENU
LCD-SLP LED Indicators
Lights to indicate the presence of AC voltage input.
Lights when the system is in alarm, flashes until the alarm is acknowledged.
Lights to indicate a hazard condition, flashes until it is acknowledged.
Lights when a supervisory condition exists, flashes until the trouble acknowledge is
performed.
Lights to indicate a trouble condition, flashes until the trouble is acknowledged.
Lights when the System Silence is pressed.
Flashes when the System Silence is pending.
LCD-SLP Audible/Visual Condition Indicators
Audible/Visual Status Indicators
Alarm situations are indicated by a one-half second ON and one-half second OFF
pattern from the system sounder & the illumination of the red alarm LED.
Hazard situations are reported by a Coded 4 pattern.
Supervisory events are indicated by a continuous tone from the system piezo sounder
and the illumination of the supervisory LED.
Trouble conditions are indicated by a continuous tone from the system piezo sounder
and the illumination of the YELLOW trouble LED.
LCD-SLP Non-Releasing Fire Switches
Toggles the Menu ON and OFF. (See Notes 1 and 2)
Initiates a fire drill. (See Note 1 and 2)
Initiates a System Reset, as well as five User-Defined switches.
Custom indication & switch function. This switch must be programmed in CAMWorks.
(See Note 1)
SILEN C E D
DR ILL
R E SET
Description
Description
NOTES
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents