For NCA-2 connections, see Appendix I.
H.1 Capabilities
ACS annunciators communicate with the control panel on the ACS Mode interface (TB3 on the NCA). Annunciators can be programmed to
annunciate the status of addressable devices, software zones, system control functions or shadowing ACS points mapped to an
AM2020/AFP1010. The NCA supports up to 96 points per annunciator address. The ACS devices can be programmed as either 64 or 96
points depending on which ACS series is being used. Up to 32 devices can be driven by the EIA-485 communications output, all addresses
combined. Two-way communications can occur with only one annunciator per address; other devices on the same address must be config-
ured as "Receive Only".
H.2 Connecting the EIA-485 Circuit
EIA-485 wiring is connected to TB3 of the NCA (ACS Mode interface) as shown in the accompanying illustration.
See Section 4.3 for details and notes about EIA-485 requirements.
H.3 Providing Power to Annunciators
The annunciator's power supply is connected to +24V non-resettable power on TB1 of the NCA; any of the three
positive terminals and three negative terminals can be used to connect power to the ACS. A typical configuration is
shown in the accompanying illustration.
The current which can be drawn from these power-limited terminals depends on which supply is being used to
power the NCA; the annunciators may also be powered directly from the power supply that is powering the NCA,
using the power-limited non-resettable 24VDC terminal. (See the NCA Manual for details.)
The power run to the annunciator does not require a Power Supervision Relay. Loss of power is inherently super-
vised through a Communications loss. This 24 VDC output is supervised, power-limited, filtered, and non-resetta-
ble.
H.4 Programming the NCA for Remote Annunciation
NOTE: Annunciator points must be programmed from the NCA before the annunciators will function. To program the annunciators into NCA
memory, and to map system points and software zones to annunciator points, refer to the NCA Manual. The NCA employs the following format
for annunciator points:
Annunciator address
In the range of 1-32, as set
on the annunciator's rotary
decimal switches.
NOTE: When using the NCA to annunciate points on the AM2020/AFP1010 over the network, enable state reporting in the AM2020/AFP1010
panel for control module points and "NONA"/"NOA" module points; refer to the NCA Manual for instructions.
50

Appendix H: NCA Systems (UL 8th)

A(xx) P(yy)
ACM-24AT,
Points 1-24
ACM-48A,
Points 1-48
*Note: Points 65-96 are not used unless ACS device is programmed for 96 points.
ACM-16AT,
Points 1-16
ACM-32A,
Points 1-32
Annunciator Points per Module
First AEM-24AT,
Second AEM-24AT,
Points 25-48
Points 49-72*
AEM-48A,
Points 49-96*
First AEM-16AT,
Second AEM-16AT,
Points 17-32
Points 33-48
AEM-32A,
Points 33-64
TB3 on NCA
TB1 on NCA
Third AEM-24AT,
Points 73-96*
Third AEM-16AT,
Points 49-64
ACS Manual — P/N 15842:N3 5/4/2022