AIM-200 Point Annunciation
G.7 AIM-200 Point Annunciation
The ACS can annunciate up to 192 intelligent devices mapped by an AIM-200. The
AIM-200 must be installed directly to the right of the control panel.
This option provides annunciation of up to 256 points for the System 5000; one pos-
sible configuration is shown in the accompanying illustration.
Note that an annunciator controls standard System zones; it cannot be used to execute
manual ON/OFF control of intelligent AIM-200 points.
Annunciator Address 1
8 control panel points (control panel point shift not an option).
8 unusable points (redundant AIM-200 points).
48 points mapped to the next six modules installed in the System (which can
also be AIM-200s for annunciation of their eight software zones).
Annunciator Address 2
Intelligent Detectors, addressed 1-64, on the AIM-200 installed next to the
control panel.
Annunciator Address 3
Addressable Modules, addressed 1-64, on the AIM-200 installed next to the
control panel.
Annunciator Address 4
Intelligent Detectors, addressed 65-96, followed by Addressable Modules,
addressed 65-96, on the AIM-200 installed next to the control panel. The control
panel's programming manual provides programming instructions for this option.
Refer to program choice "AIM(256)".
NOTE: AIM-200 detector and module addresses 97, 98, and 99 may be
used, but cannot be point-annunciated.
ACS Manual — P/N 15842:N3 5/4/2022
System 5000 Systems: ACM-16AT and ACM-32A Only (UL 8th)
8 control
panel points
8 unusable
AIM-200 points
48 points mapped to modules in
positions 3, 4, 5, 6, 7 and 8