Appendix D: Am2020/Afp1010 Systems (Ul 8Th); D.1: Capabilities; D.2: Connecting The Eia-485 Circuit; D.3: Providing Power To Annunciators - Honeywell NOTIFIER ACS Series Manual

Annunciator control system
Table of Contents

Advertisement

D.1 Capabilities
When installed with an AM2020/AFP1010, annunciators can be programmed to annunciate the status of addressable devices, software
zones, and several system control functions:
Devices
– Photo, Ion, and Heat Intelligent Detectors
– Monitor and Control Modules
– Addressable Manual Pull Stations
Refer to the appropriate FACP manuals for more information.
Software Zones 1-240
System Controls
– Acknowledge/Step (the ACK/STEP key)
– Signal Silence
– System Reset
– Lamp Test
XP Series Transponder System
– Power and Audio Supply Supervision
– XP Series Form-C Alarm and Trouble Relays
– Control, Monitor, and Relay Module Circuits
D.2 Connecting the EIA-485 Circuit
The AM2020/AFP1010 must include an intelligent Serial Interface Board
(SIB-2048A/SIB-NET). Up to two EIA-485 circuit loops may be connected to the SIB as
shown in the accompanying illustration.
See Section 4.3, "EIA-485 Wiring Specifications" for details and notes about EIA-485
requirements.
Software Requirements: ACM-16AT, ACM-32A
The AFP1010 is fully compatible with ACS annunciators. The AM2020 must be operat-
ing with software with the following part numbers (or greater) shown in Table D.1.
AM2020 Board
Central Processing Unit (CPU-2020)
Display Interface Assembly (DIA-1)
Loop Interface Board (LIB-200)
Loop Interface Board (LIB-200A/LIB-400)
NOTE: Each ROM in software installed in the AM2020/AFP1010 must be part of the same software combination.
D.3 Providing Power to Annunciators
AM2020/AFP-1010 panels use Main Power Supply MPS-24A. The annunciator's power supply is con-
nected to +24V non-resettable power; use the middle two pins on TB3 of the MPS-24A as shown in the
accompanying illustration. Do not cut jumper JP5! No more than 3A can be drawn from these power-lim-
ited terminals in standby or alarm.
The power run to the annunciator does not require a Power Supervision Relay. Loss of power is inherently
supervised through a Communications loss. This 24 VDC output is supervised, power-limited, filtered, and
non-resettable.
ACS Manual — P/N 15842:N3 5/4/2022

Appendix D: AM2020/AFP1010 Systems (UL 8th)

73123 and higher or M2.7 and higher
73132 and higher or M2.7 and higher
73117 and higher or M2.7 and higher
M2.7 and higher
Table D.1 AM2020 Software Compatibility
ROM Part Number
EIA-485 Circuit 1
Ground
SIB-2048A/SIB-NET
EIA-485 Circuit 2
Note:
1.EIA-485 circuit rated 5.5 VDC max.,
60 mA max.
2.If using the SIB's resistor switch, refer to
the AM2020/AFP1010 manual.
P5 on AM2020
24 VDC
TB3 on
MPS-24A
37