D.7: Acs Program Mapping - Honeywell NOTIFIER ACS Series Manual

Annunciator control system
Table of Contents

Advertisement

AM2020/AFP1010 Systems (UL 8th)
Dip Switch
Switch #
1
Manual override: Set "ON" for this application.
2, 3
Expanders installed: Set these switches according to how many expanders are installed at the address. See Section 5.12.3,
"Configuring Number of Expander Modules" for ACM-24AT/ACM-48A; see Section 5.13.3, "Configuring Number of Expander
Modules" for ACM-16AT/ACM-32A.
4
Not used; set to OFF
5
Receive Only: Set this switch "OFF" for this application.
6
Piezo Disable: Set this switch "ON" for this application unless the annunciator and AMG-1 are not located adjacent to the
AM2020/AFP1010. In that case, the piezo must sound and the switch must be set to "OFF".
7
Switch Inhibit: Set this switch "OFF" for this application.
8
Flash Inhibit: Set this switch "OFF" for this application.
D.7 ACS Program Mapping
ACS points "track" or follow those system points they are programmed to annunciate; the annunciator points do not latch. Table D.2, which
follows, lists how the ACS annunciates various devices and functions.
Point Type
Control Module
XPC Circuit
XPR Circuit
XPIQ Speaker and
Telephone/Strobe
Circuits
Monitor Module
XPM Circuit
XPIQ Monitoring
XP5-M
Intelligent Detector
Software Zone
1
ACK/STEP
SIGNAL SILENCE
2
SYSTEM RESET
2
LAMP TEST
1
In older systems, if the monitor module or XPM-8 circuit is programmed as a supervisory point (SPSU), illumination of the trouble LED
will occur for both trouble and supervisory conditions. The exact status of the point (trouble versus supervisory condition) can be read at the
AM2020/AFP1010 control panel.
Prior to software release M2.8, supervisory points do not activate the point active LEDs of an annunciator.
2
With the AM2020/AFP1010, the functions of ACK/STEP, SIGNAL SILENCE, SYSTEM RESET and LAMP TEST may be assigned
(mapped) to multiple annunciator points.
NOTE: Control Switches marked "not used" will still function as local LAMP TEST switches for their respective LEDs.
40
ACM-24AT Function
ACM-48A or ACM-32A Module &
AEM-48A or AEM-32A Expander
Active LED
Indicates on/off status of module or
circuit
Indicates alarm status of module or
1
circuit
Indicates alarm status of detector
Indicates active status of software
zone
Indicates System Alarm
1
Not used
Indicates System Alarm
Not used
Table D.2 Annunciator Program Mapping with AM2020/AFP1010
Eight-Point Shift: Set to "OFF".
ACM-24AT or ACM-16AT Module and
AEM-24AT or AEM-16AT Expanders
Trouble LED
Indicates trouble status of module or
circuit
Indicates trouble status of module or
1
circuit
Indicates trouble status of detector
Indicates System Trouble
Indicates System Trouble
Indicates Signals Silence
Indicates System Trouble
Not used
ACS Program Mapping
ACM-16AT Function
Control Switch
Turns module on/off
Not used
Not used
Not used
ACK/STEP key
SIGNAL SILENCE key
SYSTEM RESET key
LAMP TEST key
ACS Manual — P/N 15842:N3 5/4/2022

Advertisement

Table of Contents
loading

Table of Contents