TEMPERATURE SENSOR (C7110D1009A,
ONLY)
Table 1. Temperature sensor accuracy
ambient
max. error
temperature
15.5 °C (60 °F)
±0.29 °C (±0.52 °F)
18.3 °C (65 °F)
±0.27 °C (±0.49 °F)
21.1 °C (70 °F)
±0.27 °C (±0.49 °F)
26.7 °C (80 °F)
±0.27 °C (±0.49 °F)
29.5 °C (85 °F)
±0.29 °C (±0.52 °F)
Electronic offset compensation at 23 °C = 0.5 K.
80 K
70 K
60 K
50 K
40 K
30 K
20 K
10 K
30
40
50
60
0
10
temperature (degrees)
Fig. 15. Temperature vs. resistance for 20 kΩ sensor
Temperature Setpoint Adjustment
(C7110D1009A)
Depending on the type of wheel in use on the C7110D1009A,
the corresponding controller must be set for either the relative
or the absolute scale. The relation between setpoint and
resistance is given in Table 2.
The accuracy of resistance is:
5% in middle position, e.g., 5225 Ω to 5775 Ω
▪
10% in end position, e.g., 9450 Ω to 11550 Ω.
▪
Table 2. Setpoint values versus resistances
relative scale (Kelvin)
nominal
setpoint
resistance (Ω)
-5
9574
-4
8759
-3
7944
-2
7130
-1
6315
0
5500
1
4685
2
3870
3
3056
4
2241
5
1426
C7110C1001A, C7110D1009A WALL MODULES – PRODUCT DATA
nominal
resistance (Ω)
31543
27511
24047
18490
16264
70
80
90 100 110
° F
20
30
40
°C
absolute scale (°C)
nominal
setpoint
resistance (Ω)
12
9958
14
8979
16
8001
18
7022
20
6043
22
5065
24
4086
26
3107
28
2129
30
1150
7
EN0B-0735GE51 R0317