Troubleshooting The Blower Installation - Cisco 12416 Installation And Configuration Manual

Cisco systems bridge/router installation and configuration guide
Hide thumbs Also See for Cisco 12416:
Table of Contents

Advertisement

Removing and Replacing Blower Modules

Troubleshooting the Blower Installation

Step 1
Step 2
Step 3
Cisco 12016, Cisco 12416, and Cisco 12816 Router Installation and Configuration Guide
7-28
Use the following procedure to troubleshoot a blower module if it is not operating
properly after installation.
Be sure the router is powered on and that all power cords are connected properly.
Loosen the captive screws and reseat the blower module to the chassis.
Retighten the captive screws to ensure the blower module is properly seated
to the backplane connector.
Check the blower module status indicators:
OK (green)—Indicates that the blower module is operating normally. This
indicator should light as soon as the blower module is installed and receives
power from the backplane connector.
If this indicator remains on, and the blower module fans fail to operate
after several attempts to reseat the blower module, replace it with a spare.
If the spare blower module also fails, power off the router and contact a
Cisco service representative for assistance.
FAIL (red)—During normal operation, this indicator remains off. If this
indicator is on, the system has detected a fan failure or other fault in the
blower module.
If this indicator remains on, and the blower module fans fail to operate
after several attempts to reseat the blower module, replace it with a spare.
If the spare blower module also fails, power off the router and contact a
Cisco service representative for assistance.
Chapter 7
Maintaining the Router
OL-11495-01