False Alarm Immunity

The following table represents the minimum distance at which the detector did not false alarm or show
any signs of instability during exposure to the sources listed. Additionally, the sensitivity to a one
square foot n-Heptane reference pan fire in the presence of the false fire source is listed.
False Fire Source
Direct Sunlight
Modulated Sunlight
Modulated Arcwelding
Continuous Arcwelding
Resistive Electric Heater
Flourescent Lamp
Halogen Lamp
Sodium Vapor Lamp
Pelican Flashlight
Incandescent Lamp
Honeywell
Minimum Distance
with no Alarm
No Alarm
No Alarm
3 feet 9 inches / 1.14 meters
3 feet 9 inches / 1.14 meters
1 foot / 30.48 centimeters
1 foot / 30.48 centimeters
1 foot / 30.48 centimeters
1 foot / 30.48 centimeters
1 foot / 30.48 centimeters
1 foot / 30.48 centimeters
Installation and Operating Manual
Sensitivity to a 1' x 1' n-Heptane
reference pan fire in the
presence of the false fire source
50 feet /15.24 meters
25 feet / 7.62 meters
Source at 15 feet / 4.57 meters
Fire at 30 feet / 9.14 meters
Source at 15 feet / 4.57 meters
Fire at 30 feet / 9.14 meters
Source at 3 feet / 91.44 centimeters
Fire at 200 feet / 60.96 meters
Source at 3 feet / 91.44 centimeters
Fire at 200 feet / 60.96 meters
Source at 7 feet / 2.13 meters
Fire at 200 feet / 60.96 meters
Source at 3 feet / 91.44 centimeters
Fire at 200 feet / 60.96 meters
Source at 3 feet / 91.44 centimeters
Fire at 200 feet / 60.96 meters
Source at 3 feet / 91.44 centimeters
Fire at 200 feet / 60.96 meters