A U TO M AT I C C O N T R O L U N I T, O M D 8 0 0
7.2.2.3 System Configuration
In the System Configuration subpage user can configure parameters of the monitored lines; see Table
7.3. The parameter selection and its value changes are made by using UP, DOWN and ENTER keys.
The System Configuration subpage requires a password. Password consists of 4 numbers, it is given by
UP, DOWN and ENTER keys. The default password is 0001. Please, change the default password to your
own. The password is valid one minute after leaving the password protected subpage. If the password
is forgotten or lost, please, contact product support.
Password Authentication
0000
Back
Forward
System Configuration
Ext VT Secondary Voltage
Secondary Load
Generator Usage
Figure 7.9
System Configuration requires a password
Parameter
Rated Voltage
Rated Frequency
Number of Phases LN1
Number of Phases LN2
Ext. Voltage Transformer
Ext. VT Primary Voltage
Ext. VT Secondary Voltage
Secondary Load
Generator Usage
Line Priority
Changeover Switch Type
Manual Back Switching
Generator Shutdown
Table 7.3
Parameters and values of the System Configuration
System Configuration
Rated Voltage
Rated Frequency
Number of Phases LN1
Edit
System Configuration
9/13
Line Priority
Changeover Switch Type
Manual Back Switching
Values
100/57 V - 115/66 V - 120/70 V - 208/120 V - 220/127 V -
230/132 V -
240/138 V - 277/160 V - 347/200 V - 380/220 V - 400/230 V -
415/240 V - 440/254 V - 480/277 V
50 Hz and 60 Hz
3 phases with N / 3 phases without N / 1 phase
3 phases with N / 3 phases without N / 1 phase
Absent / Present
100/57 V - 115/66 V - 120/70 V - 208/120 V - 220/127 V -
230/132 V -
240/138 V - 277/160 V - 347/200 V - 380/220 V - 400/230 V -
415/240 V -
440/254 V - 480/277 V - 500/288 V - 550/317 V - 600/347 V -
660/380 V - 690/400 V - 910/525 V - 950/550 V - 1000/577 V -
1150/660 V
100/57 V - 115/66 V - 120/70 V - 208/120 V - 220/127 V -
230/132 V -
240/138 V - 277/160 V - 347/200 V - 380/220 V - 400/230 V -
415/240 V - 440/254 V - 480/277 V
Not Used / Opening Only / Opening And Closing / Opening
Pulse /
Opening/Closing Pulse
No Generator / Generator In Use
Line 1 – Switch I / Line 2 – Switch II / No Line Priority
Automatic OTM_C_D / Motorized OTM_C
Off / On
Off / On
1/13
System Configuration
Number of Phases LN2
Ext Voltage Transformer
Ext VT Primary Voltage
12/13
System Configuration
Changeover Switch Type
Manual Back Switching
Generator Shutdown
31
6/13
13/13