4.3.2
Wiring SLC Devices in Style 6 & 7 (Class A)
Configuration
Figure 4-3 illustrates how to wire the SLC loop for Style 6 or Style 7 Class A
installations.
Note: Style 6 does not require the use of isolator modules.
Note: No t-taps allowed on Class A SLC loops.
For proper system supervision do not use looped wire under terminals marked SLC + and –
of the SLC device connectors. Break wire runs to provide supervision of connections.
4-4
Figure 4-3 Class A SLC Configuration