Electrical Specifications; Power Requirements; Current Ratings - Honeywell SILENT KHIGHT SK-FFT Installation And Operation Manual

Fire fighters telephone
Table of Contents

Advertisement

SK-FFT Installation and Operation Manual
2.4

Electrical Specifications

2.4.1

Power Requirements

Voltage for the SK-FFT must be a power-limited, filtered, non resettable nominal 24
VDC source. The voltage source must be within the range of 17-29 VDC.
SLC Circuits
Audio Circuits
2.4.2

Current Ratings

Maximum current ratings for determining backup battery requirements for alarm
(active) and standby conditions over the input voltage range of 17-29 VDC are shown
in Table 2-2.
SK-FFT
FFT-24
2-4
Table 2-1: Electrical Ratings
Circuits
Voltage
32 V
17 V
Table 2-2: SK-FFT Current Draw
Current
150 mA
53 mA
Active
Standby
230 mA
120 mA
25 mA
10 mA
54711

Advertisement

Table of Contents
loading