3. 8. 6 Power button functions

For the device's READY mode, the power button can be assigned different functions
Register
type
Holding
Holding
Holding
Input
The power button function is described in the below table.
Value
0
1
2
3
4
5
TR80 is primarily a display, not a control device. Therefore, further settings and some con-
figuration on the master controller or DALI side are required for these functions to work.
Relevant TR80 settings:
Departure delay: This is a parameter on the TR80 with a default of 10 seconds. When the
power-button press is to activate 'Lights Off' command, the display will count down
from this value before executing the command. This is to ensure the room tenant is not
left in the dark when exiting.
Scene settings for lights on & off: If a DALI64 sensor is on port 2, the TR80 can turn the
lights on/off directly without involving the master controller. It will do that by sending
'recall scene' commands to the DALI64 sensor. Therefore, it is necessary to set which
scenes numbers are configured on the DALI side to turn the lights fully off or fully on.
These settings are detailed in section 3.11.6.
If a scene number is not set for Lights On or Lights Off functions, TR80 will send
absolute light level commands (100% / 0%) instead.
TR80 - Installation and Operation Guide
Relative
Absolute
Address
Address
2110
42111
R/W
2111
42112
R/W
115
2118
R/W
102
30103
R
Function
No Function
Dark Mode
Sleep Mode
Switch Lights On Off Toggle
Switch Lights On
Switch Lights Off
Config
Dir
Name
parameter
Power Button
Short Press
108
Function
Power Button
long Press
109
Function
Departure
42119
delay
Power Button
user
-
command
The power button will not be enabled
The power button activates dark mode.
The power button switches the device to SLEEP mode.
With each tap, the power button toggleson/off commands to all defined
lighting groups.
On every tap, the power button sends on command to all defined lighting
groups.
On every tap, the power button sends off command to all defined lighting
groups.
Type
Range
0: No function
1: Dark Mode
2: Sleep Mode
enum
3:SwitchLightsOnOff
Toggle
4: SwitchLights On
5: SwitchLights Off
enum
Same as above
secs
0-300 seconds
0: default
1: Lights On
enum
activated
2: Lights Off
activated
Description
.
Default
value
2
0
10 s
42

Hide quick links: