3. 8. 4 LCD Symbols

Most symbols on the LCD are activated with internal logic depending on current status (occu-
pancy etc). Other symbols can be only activated via Modbus by a master controller, as
explained below.
Register
type
Holding
Holding
Holding
Holding
The alarm symbol is normally activated by internal fault conditions (see
master controller can override this as above.

3. 8. 5 Text override

If a non-zero value is written to this register, the upper screen area will display the selected
scrolling text. This overrides any other text that might otherwise be displayed.
Register
type
Holding
41
Relative
Absolute
Address
Address
1102
41103
R/W
1103
41104
R/W
1104
41105
R/W
1105
41106
R/W
Relative
Absolute
Address
Address
1106
41107
R/W
Dir
Name
Window open symbol
ECO symbol
Alarm symbol
Day/night symbol
Dir
Name
Text override
enum
TR80 - Installation and Operation Guide
Type
Range
0: off
Enum
1: on
2: blink
0: off
Enum
1: on
2: blink
0: off
1: on
Enum
2: blink
3: auto
0: off
1: sun symbol on
Enum
2: moon symbol on
3: sun symbol blink
4: moon symbol blink
Fault
Conditions). The
Type
Range
0: none
1: "Fan Off"
2: "Clg/Htg Off"
3: "Window Open"
4: "Condensation"
5: "Fire"
6: "Service required"
Default
value
0
0
3
0
Default
value
0

Hide quick links: