Honeywell TR80UWD Installation And Operating Manual page 69

Wall module
Table of Contents

Advertisement

Config
parameter
Name
number
13
External sensor
type
14
On-board sensor
temp offset
15
On-board humidity
sensor offset
16
Dnd Mur enable
999
Reset to defaults
Note: Config from MAster controller details will be available in Master Controller
documents.
62
Type/
Range
Unit
(min-Max)
enum
"0: NONE
1: NO contact
2: NC contact
3: 0-10 Vdc
4: 2-10 Vdc
5: Raw Ohms
6: NTC10K
7: NTC20K"
signed
-10.0 ... +10.0 K
signed
-10 ... +10 %Rh
enum
"0: disabled
1: DnD enable
2: MuR enable
3: Dnd/Mur enable"
bool
Default
0
NO : 0=open, 1 = closed
NC : 0= closed, 1 = open
0
0
1
0
Resets some settings to default values.
Primarily modbus comms settings.
Exact list to be compiled later