Safety Provisions - Honeywell 7800 Series Manual

Relay modul
Hide thumbs Also See for 7800 Series:
Table of Contents

Advertisement

f. Purge card is not installed or removed.
g. Purge card is bad.
7. POSTPURGE Period
a. Preignition Interlock does not close within five-
seconds and opens after five-second time period.
b. Ignition/pilot valve/intermittent pilot valve termi-
nal is energized.
INTERNAL HARDWARE STATUS MONITORING
The RM7800 checks the purge card for correct parity to
prevent purge timing shifts and circuitry failures. It also
analyzes the integrity of the configuration jumpers and
internal hardware. The POWER LED blinks every four
seconds, signifying an internal hardware check.
CLOSED LOOP LOGIC TEST
The test verifies the integrity of all safety critical loads,
terminals 8, 9, 10 and 21. If the loads are not energized
properly; i.e., the main valve terminal is powered during
PREPURGE, the RM7800 will lockout on safety shutdown.
The RM7800 must react to input changes but avoid the
occurrence of nuisance shutdown events. Signal condition-
ing is applied to line voltage inputs to verify proper operation
in the presence of normal electrical line noise such as
transient high voltage spikes or short periods of line drop-
out. Signal conditioning is tolerant of synchronous noise
(line noise events that occur at the same time during each
line cycle).
DYNAMIC AMPLI-CHECK™
Dynamic AMPLI-CHECK™ circuitry tests the flame
signal amplifier during burner operation and shuts down the
RM7800 if the flame amplifier fails.
DYNAMIC FLAME AMPLIFIER AND SHUTTER
CHECK
Self-checking circuitry tests all electronic components
in the flame detection system and amplifier 10 to 12 times
per minute and shuts down the RM7800 if the detection
system fails.
DYNAMIC INPUT CHECK
All system input circuits are examined to verify the
RM7800 is capable of recognizing the true status of external
controls, limits and interlocks. If any input fails this test, a
safety shutdown occurs and the fault is annunciated.
DYNAMIC SAFETY RELAY TEST
Checks the ability of the dynamic safety relay contacts
to open and close. It also verifies that the safety critical
loads, terminals 8, 9, 10 and 21, can be de-energized, as
required, by the Dynamic Self-Check logic.
DYNAMIC SELF-CHECK SAFETY CIRCUIT
The microcomputer tests itself and related hardware
while at the same time the safety relay system tests the
microcomputer operation. If a microcomputer or safety
relay failure occurs and does not allow proper execution of
the self-check routine, safety shutdown will occur and all
safety critical loads will be de-energized.
PRINCPLE TECHNICAL FEATURES • SAFETY PROVISIONS
c. Main valve terminal is energized.
d. Internal system fault.
e. Purge card is removed.
f. Purge card is bad.

Safety Provisions

EXPANDED SAFE-START CHECK
The conventional safe-start check, which prevents burner
start-up if flame is indicated at start-up, is expanded to include
a flame signal check during STANDBY, a preignition inter-
lock check, an interlock check, and a safety critical load
check.
HIGH FIRE PURGE AND LOW FIRE START
SWITCH TESTS
High Fire Purge Switch Test (RM7800E,L) examines the
Purge Position Interlock Switch at the moment the firing rate
motor is commanded to the high fire position. If the switch is
bypassed, welded or otherwise closed prematurely, the sys-
tem will automatically add 30 seconds to allow additional
drive time for the firing rate motor to reach or near the open
position before starting the purge timing; otherwise, purge
timing starts when the High Fire Switch is closed. This switch
will also cause a hold (four minutes, fifteen seconds) condi-
tion when the switch is open before purge or opens during
purge. The RM7800E,L will lockout and annunciate an
alarm if the switch fails to close within the hold time period.
Low Fire Start Switch Test examines the Low Fire Start
Switch at the moment PREPURGE is completed. If the
switch is bypassed, welded or otherwise prematurely closed,
the system automatically adds 30 seconds to allow the firing
rate motor additional time to reach or near the low fire start
position before ignition trials; otherwise, ignition trials start
after the Low Fire Switch closes. The test also is used to prove
that the firing rate motor is at low fire position throughout
the ignition trial period. This switch will also cause a hold
(four minutes, fifteen seconds) condition if the switch opens
after purging is complete. The RM7800 will lockout and
annunciate an alarm if the switch fails to close within the
hold time period.
MANDATORY PURGE
If lockout occurs after the initiation of ignition trials,
(or at anytime during a sequence when the fuel valves may
have been energized), a mandatory POSTPURGE period
is imposed.
OFF CYCLE (STANDBY OR PREPURGE) FLAME
SIGNAL CHECK
The flame detection subsystem (flame detector and ampli-
fier) is monitored during STANDBY. If a flame simulating
condition or an actual flame exists, a system hold occurs and
start-up is prevented. If the flame signal exists at any time
after the first 40 seconds of STANDBY, a safety shutdown
will occur and be annunciated. A shutter-check amplifier and
self-checking detector are energized for the first 40 seconds
during STANDBY and the last two seconds before exiting
STANDBY. If a flame exists, a safety shutdown occurs.
9
RM7800E,G,L,M
65-0117—2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rm7800eRm7800gRm7800lRm7800m

Table of Contents