Selectable Message
(Second Line)
◊Expanded Annun.↔
◊Expanded Annunciator (EA not connected)<
◊Current Status (CS:)
a
◊Valve Closure (Valve Close)
◊Burner Switch (Burner Sw.)
◊Operating Control (OperControl)
◊Auxiliary Limit (Aux Limit 1)
◊Auxiliary Limit (Aux Limit 2)
◊Low Water Cutoff (LWCO)
◊High Limit (High Limit)
◊Auxiliary Limit (AuxLimit 3)
◊Oil Selection Switch (Oil Select)
◊High Oil Pressure Switch (Hi OilPres)
◊Low Oil Pressure Switch (LowOilPres)
◊High Oil Temperature Switch (Hi OilTemp)
◊Low Oil Temperature Switch (LowOilTemp)
◊Atomizing Switch (Atomize Sw)
◊Gas Selection Switch (Gas Select)
◊High Gas Pressure Switch (Hi GasPres)
◊Low Gas Pressure Switch (LowGasPres)
◊Airflow Switch (Airflow Sw)
◊Auxiliary Interlock (Aux ILK 4)
◊Auxiliary Interlock (Aux ILK 5)
◊EA Fault Code
◊Software Revision (SW Rev.)
a
Expanded Annunciator Diagnostic Current Status Messages can be reviewed in 7800 SERIES System Annunciation
Diagnostics and Troubleshooting, form 65-0118, Table 7.
RUN/TEST SWITCH FUNCTIONS
The Run/Test Switch is located on the top side of the
RM7800, see Fig. 27. The Run/Test Switch allows the
burner sequence to be altered as follows:
1. In Prepurge Drive To High Fire Position, the Run/
Test Switch, when placed in the TEST position, will hold
in PREPURGE with the firing rate motor in the High Fire
position.
2. In the measured PREPURGE sequence, the Run/Test
Switch, when placed in the TEST position, will cause the
PREPURGE timing to stop. The firing rate motor will be in
the High Fire position.
3. In Prepurge Drive to Low Fire position, the Run/Test
Switch, when placed in the TEST position, will hold the
burner sequence in PREPURGE with the firing rate motor in
the Low Fire position.
4. In PFEP, the Run/Test Switch, when placed in the
TEST position, will stop the timer during the first eight
seconds when a ten second PFEP is selected or during the
first three seconds when a four second PFEP is selected,
allowing pilot-turn-down test and other burner adjustments
to be made. This activates a fifteen second flameout timer
that permits pilot flame adjustment without nuisance safety
shutdowns. The Run/Test Switch will be ignored during
TABLE 5—EXPANDED ANNUNCIATOR MESSAGES.
Display Value
(Second Line)
EA Message<
T4
ON or OFF<
T5
ON or OFF<
T6
ON or OFF<
T7
ON or OFF<
T8
ON or OFF<
T9
ON or OFF<
T10
ON or OFF<
T11
ON or OFF<
T12
ON or OFF<
T13
ON or OFF<
T14
ON or OFF<
T15
ON or OFF<
T16
ON or OFF<
T19
ON or OFF<
T17
ON or OFF<
T18
ON or OFF<
T19
ON or OFF<
T20
ON or OFF<
T21
ON or OFF<
T22
ON or OFF<
nnn<
nnnn<
PFEP for the RM7800E,L if terminals 8 and 9 or 9 and 21
are jumpered.
5. During RUN, the Run/Test Switch, when placed in
the TEST position, will drive the firing rate motor to the
Low Fire position.
NOTE: When RM7800 is switched to the TEST mode, it will
stop and hold at the next Run/Test Switch point in the
operating sequence. Make sure that the Run/Test Switch is
in the RUN position before leaving the installation.
!
WARNING
Do not use the Run/Test switch during the Pilot
Flame Establishing Period for the RM7800G,M
when using Direct Spark Function.
SELECTABLE SITE-CONFIGURABLE JUMPERS
The RM7800 has three site-configurable jumper options,
see Fig. 32 and Table 6. The site-configurable jumpers
should be clipped with side cutters and the resistors re-
moved from the Relay Module.
31
RM7800E,G,L,M
OPERATION
First Line
Message
↓EA
↓EA
↓EA
↓EA
↓EA
↓EA
↓EA
↓EA
↓EA
↓EA
↓EA
↓EA
↓EA
↓EA
↓EA
↓EA
↓EA
↓EA
↓EA
↓EA
↓EA
↓EA
↓EA
65-0117—2