EC7830A, RM7830A, EC7850A, RM7850A 7800 SERIES RELAY MODULES

SPECIFICATIONS

Electrical Ratings (See Tables 3A, 3B, 3C and 3D):
Voltage and Frequency:
RM7830A and RM7850A:
120 Vac (+10/-15%), 50/60 Hz (±10%).
EC7830A and EC7850A:
220/240 Vac (+10%/-15%), 50/60 Hz (±10%)
Power Dissipation: 10W maximum.
Maximum Total Connected Load: 2000 VA.
Fusing Total Connected Load: 15A maximum, Fast Blow,
type SC or equivalent.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to 140°F (-40°C to +60°C).
Storage: -40°F to 150°F (-40°C to +66°C).
Humidity: 85% relative humidity continuous, noncon-
densing.
Vibration: 0.5G environment.
SIL 3 Capable:
SIL 3 Capable in a properly designed Safety Instrumented
System. See form 65-0312 for Certificate Agreement
Approvals
Federal Communications Commission:
Part 15, Class B, Emissions.
Exida: IEC/EN 61508:2010 Parts 1-7, SIL 3 capable.
AGA Certificate # 5097
EAC Russia
Factory Mutual Approved: Report No. 1V9A0.AF (for
RM7830A1003, RM7830A1029, RM7850A1001,
RM7850A1019, RM7830A2003, RM7830A2029,
RM7850A2001, RM7850A2019)
European Directives
Gas Appliances Regulation: 2016/426/EU GAR
Low Voltage Directive: 2014/35/EU LVD.
EMC Directive: 2014/30/EU EMC (Immunity Emission
conformity can only be verified in combination with
the appliance).
GASTEC: certificate # 18GR0996/00, PIN 0063CT1466
Applicable Standards:
EN 298:2012 Automatic burner controls
EN 60335-2-102 Household and similar electrical
appliances
EN 746-2 Industrial thermo-processing - fuel handling
systems
Please note the following to comply with EN60730 for
remote mounting of the KDM and/or remote reset module.
It is necessary to provide electrical separation using
insulation at least equivalent to double or reinforced
insulation. This can be accomplished by either:
1. Optically isolating the communication and/or
remote reset lines from the control cabinet or
2. Providing physical separation from the
communication and/or remote reset lines using
electrical conduit and a 204718A Remote Display
Cover Assembly or other suitable enclosure that
meets NEMA4 class of protection.
32-00198—01

INSTALLATION

When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and
marked on the product to make sure the product is
suitable for the application.
3. Installer must be a trained, experienced, flame
safeguard service technician.
4. After installation is complete, check out the product
operation as provided in these instructions.
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death or property
damage.
Carefully follow safety requirements when
installing a burner control.
WARNING
Electrical Shock Hazard or Equipment Damage
Hazard.
Can cause severe injury, death or equipment
damage.
Disconnect power supply before beginning
installation. More than one disconnect may be
involved.
Continuous Operation Note
Non-check amplifiers cannot be used in continuous
operation (per EN298). For continuous operation only
ampli-check or shutter/self-check flame amplifiers are
used.
Non-check amplifiers trigger the device to automatically
recycle after 24 hours when in a continuous run mode.
IMPORTANT
1. Wiring connections for the relay modules are unique;
refer to Fig. 4 and 5 or the appropriate Specifications
for individual subbase wiring.
2. Wiring must comply with all applicable codes, ordi-
nances and regulations.
3. Wiring must comply with NEC Class 1
(Line Voltage) wiring.
4. Loads connected to the EC/RM7830A and
EC/RM7850A must not exceed those listed on the
relay module label or the Specifications; see Table 1.
5. Limits and interlocks must be rated to simultane-
ously carry and break current to the ignition trans-
former, pilot valve, and main fuel valve(s).
6. All external timers must be listed or
component-recognized by authorities who have
proper jurisdiction.
7. For on-off gas-fired systems, some authorities who
have jurisdiction prohibit the wiring of any limit or
operating contacts in series between the flame
safeguard control and the main fuel valve(s).