SETTINGS AND
ADJUSTMENTS
Selectable Site-Configurable
Jumpers
The relay module has three site-configurable jumper
options, see Fig. 6 or 7 and Table 7. If necessary, clip the
site-configurable jumpers with side cutters and remove
the resistors from the relay module. The relay module
SERVICE NOTE:Clipping and removing a site-configurable jumper enhances the level of safety.
RESET
BUTTON
DUST
COVER
Fig. 6. EC/RM7830A and EC/RM7850A Relay Modules exploded view.
EC7830A, RM7830A, EC7850A, RM7850A 7800 SERIES RELAY MODULES
WIRING
SUBBASE
(Q7800A1005
plastic panel
mount version)
RUN/TEST
SWITCH
RELAY
MODULE
CONFIGURATION
JUMPERS
PURGE
TIMER
SEQUENCE
STATUS
LED PANEL
reads the settings of these configuration jumpers at
startup. After 200 hours of main valve operation, the relay
module locks the jumper settings into internal memory. If
these jumpers are changed after the 200 hours occur, the
relay module locks out. This safety function assures that
the relay module cannot be modified after it is installed in
a particular location.
If JR3 (Airflow Switch) is intact (no Airflow Switch), then a
jumper must be installed between terminals 6 and 7. If
JR3 is clipped (Airflow Switch is present), the relay module
locks out if it detects a jumper between terminals 6 and 7.
H O N E Y W E L L
17
CAPTIVE
MOUNTING
SCREW
FLAME
AMPLIFIER
M15187B
32-00198—01