Typical Disablement Messages - Honeywell GENT Vigilon Plus Series Operating Instructions Manual

Fire detection and alarm system
Table of Contents

Advertisement

Typical Disablement Messages

The following table shows some typical disablement messages and indications that may appear at the panel.
On
Flashing
Message
Indication
FARE Disabled
Fault
Zone Disabled
Disablement
at card n
Fault/Dis
Device disabled
Disablement
at card n
Sounder
Sector disabled
Disablement
at card n
Sounder
Disabled Aux
Disablement
Relay n
Master alarm(s)
Disablement
disabled
Sounder
Any changes to the setting of an automatic disablement must only be attempted by a trained engineer who is
responsible for the fire alarm system, see contact details in the Log book.
www.acornfiresecurity.com
Meaning
The Fire Alarm Routing Equipment FARE has
Fault/Dis
been Disabled.
The zone specified has been manually or
automatically disabled.
The device connected to the loop circuit has
been manually or automatically disabled.
Additional indication is given if it is a sounder
device.
The fire alarm sector on loop n has been
manually or automatically disabled.
The auxiliary relay n in the control panel has
been manually or automatically disabled.
The master alarms have been manually or
automatically disabled.
www.acornfiresecurity.com
Vigilon Plus fire alarm system
Action
If manually disabled then investigate and
if necessary re-enable FARE.
If manually disabled then investigate and
if necessary re-enable the zone.
If manually disabled then investigate and
if appropriate re-enable the device.
If manually disabled then investigate and
if appropriate, re-enable the sector.
If manually disabled then investigate and
if appropriate, re-enable the aux relay.
If manually disabled then investigate
and if appropriate, re-enable the master
alarms.
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gent vigplus-24Gent vigplus-72Gent vigplus-24-np

Table of Contents