How To Save Changes To Memory; How To View Active Events - Honeywell GENT Vigilon Plus Series Operating Instructions Manual

Fire detection and alarm system
Table of Contents

Advertisement

How to save changes to memory

If you make any changes to a Labels or Password then you
must save these to the NVM (Non Volatile Memory) or Memory
of the panel.
Changes made to labels and password can
be saved to the panel memory (NVM), this can
only be done when there are no disablements
present on the system.
The following procedures assume a customer password (PIN)
is setup at the panel.
a. Press the MENU ON/OFF button.
b. Press the F2 button to select [Set Up].
c. Press the F4 button to select [UserCode]. At the flashing
cursor using the keypad input your PIN code and then
press the Enter button.
d. Press the F4 button to select <etc> and then press the F3
button to select [Save].
The 'Save' option is only available if Access
level 2 PIN is set up.
e. Press the F2 button to select [Enter]. Observe confirmation
of data backed up.
www.acornfiresecurity.com

How to view active events

An active event is an event that is still present and has not
cleared. You can view all active Fire, Fault or Disablement
events.
a. Press MENU ON/OFF.
b. Press the F3 button to select [Info]. Ignore step c. if an
external printer is not fitted or is switched off.
c. To display the event(s): Press the F1 button to select
[Display]. Notice 'Display' appears on the display.
To print the event(s): Press the F2 button to select [Print].
Notice 'Print' appears on the display.
d. Press the F1 button to select [Active]. Notice 'Active'
appears on the display. To view events on the local panel
and on a card by card basis then press the F3 button to
select [Card], notice 'on card' appears on the display.
Enter the card number. To view events at another node in
a networked system, then you will need to know the node
number. Press the F4 button to select [Node] and enter a
node number from a range 1 to 255.
e. Press the F2 button to select [Enter]. Notice all of the
active Fire, Fault and Disablement events are displayed in
turn. Press the F2 [Previous] and F3 [Next] button to scroll
through the displayed events.
f. Press the F4 button to select [Quit], when viewing of
events is complete.
www.acornfiresecurity.com
Vigilon Plus fire alarm system
23