3. 8. 2 Monitoring

Register
type
Input
Input
Input
Unit and scale of the external sensor input depend on configured signal type:
Raw ohms
NTC
Voltage (0-10V or 2-10Vdc)
NO contact
NC contact
Temperature values on Modbus are always in degrees Celsius, even if the user has selected
Fahrenheit for display.
3.9 DO-NOT-DISTURB & MAKE-UP-ROOM
Do-not-Disturb and/ Make-Up-Room functions can be enabled individually. The button on the
TR80 will be enabled only if at least one of these functions are enabled.
Register
type
Input
Holding
37
Relative
Absolute
Address
Address
5
30006
6
30007
7
30008
Configuration
Ohms
°C
Percent
0=open, 1=closed
0=closed, 1=open
Relative
Absolute
Address
Address
3
30009
2014
42015
Dir
Name
R
External input measured value
Onboard temp sensor measured
R
value
Onboard humidity sensor
R
measured value
Unit
Scale
1
0.1
0.1
Config
Dir
Name
parameter
DnD/MuR
R
-
status
DnD/MuR
16
R/W
enable
TR80 - Installation and Operation Guide
Unit
Scale
See
See
below
below
°C
0.1
%Rh
1
Type
Range
0: none
enum
1: DnD
2: MuR
0: disabled
1: DnD enable
enum
2: MuR enable
3: Dnd/Mur enable
Default
value
0
0
0
Default
value
0
1