Auto-Reset Of Occupancy Override; Lighting Control - Honeywell TR80 Installation And Operating Manual

Wall module
Table of Contents

Advertisement

Default values allow the following overrides
From OFF
From UNOCCUPIED
From STANDBY
From OCCUPIED

3. 13. 5 Auto-reset of occupancy override

The TR80 can be configured to automatically cancel a user occupancy override when the mas-
ter occupancy mode changes (holding register 1500).
Register
type
Holding
Bit definitions:
Bit0: When master mode changes to UNOCC, cancel UNOCC override
Bit1: When master mode changes to UNOCC, cancel STBY override
Bit2: When master mode changes to UNOCC, cancel OCC override
Bit3: reserved
Bit4 When master mode changes to OCC, cancel BYPASS override
Bit5: When master mode changes to OCC, cancel OCC override
By default, all bits are set

3.14 LIGHTING CONTROL

TR 80 wall module supports upto four lighting groups. General lighting configuration parame-
ters are as follows:
Register
type
Holding
Holding
Holding
49
Override mode
none
Holiday and Bypass
Occupied, Holiday and Bypass
Unoccupied, Holiday and Bypass
Relative
Absolute
Address
Address
2508
42509
Relative
Absolute
Address
Address
2300
42301
2301
42302
1308
41309
Values
Dir
Name
Occupancy Auto
R/W
Reset
Config
Dir
Name
Parameter
Light Group
R/W
300
Count
Light
R/W
adjustment
301
step size
Group light
R/W
-
state
TR80 - Installation and Operation Guide
Config
Unit
Range
parameter
see
508
enum
below
Unit
Range
int
0...4
0: 1%
1: 2%
enum
2: 5%
3: 10%
4: 20%
Bit0: Group 1 is ON
Bit1: Group 2 is ON
bitwise
Bit2: Group 3 is ON
Bit3: Group 4 is ON
Default
value
55
Default
Value
2
3