Applications that have more complicated requirements (for example having two different cool-
ing systems within the same room) can use the advanced mode. 
Register
type
Holding
Holding
Holding
Input
Register 1201 allows a master controller to control the LED ring to indicate the status of cool-
ing and heating in the room. A constant blue means that cooling mode is active, but is not cur-
rently switched on. A constant orange means that the heating mode is active, but is not
currently switched on. The ring begins to breathe as soon as the room is cooled or heated. A
breathing green means the fan is on with no cooling and no heating. Gray means that no cool-
ing and no heating is currently possible; the central cooling and heating system is turned off or
the room user has disabled cooling or heating via a HVAC Mode overwrite. Register 1201 is
encoded as follows:
Bit representation: 000D CCBB 0000 0AAA
AAA (bits 2-0): currently active hvac mode
BB (bits 9-8): Heating outputs status
CC (bits 11-10): Cooling outputs status
D (bit 12): fan output status
Bits 2..0:
- 0: heat & cool not available (grey ring)
45
Relative
Absolute
Dir
Address
Address
2209
42210
R/W
2210
42211
R/W
1201
41202
R/W
200
30201
R
Config
Name
parameter
HVAC mode
selection
209
type
Available
210
HVAC modes
Ring
behavior
depending
-
on cooling
and heating
User selected
-
HVAC mode
TR80 - Installation and Operation Guide
Type
Range
0: disabled
enum
1: simple
2: advanced
Bit0: "AUTO"
Bit1: "HEAT"
Bit2: "COOL"
Bit3: "FANONLY"
enum
Bit4: "OFF"
Bit5: "HTG1"
Bit6: "HTG2"
Bit7: "CLG1"
Bit8: "CLG2"
0: Unknown
1: Cooling +
Heating
enum
2: Off
3: Cooling
4: Heating
5: FanOnly
0: Auto
1: Heating
2: Cooling
3: Fan-only
enum
4: Off
5: Heating 1
6: Heating 2
7: Cooling 1
8: Cooling 2
Default
value
0
15
(auto,
heat,
cool,
fan)
0
0