'Group Light State' bitmap register is used to represent which groups have at least on lamp
that is not totally off. This info typically comes from the DALI64MOD sensor.
If the DALI64 sensor is connected to port 2, the TR80 wall module will read the 'Group
Light State' directly, without any dependency on a master controller. If DALI64 sensor is
connected on port 1 (or a different lighting control system is employed) the master con-
troller will need to provide this information to the wall module.
The 'Group Light State' information in combination with 'Group Last Lever' register is used
for two purposes:
1. Light groups that are ON are indicated on the LCD with bulb symbols.
2. If LightsOn/LightsOff toggle functions are assigned to the power button, the
behaviour for the first tap of the button is determined by the group light states.
If these functions are not required/configured, there is no need for the master ontroller to
update the wall module with this information.

3. 14. 1 Light Group 1 configuration

Register
type
Holding
Holding
Holding
Holding
Set "max Scene no" to 0, to disable scene selection/activation for this group.
TR80 - Installation and Operation Guide
Relative
Absolute
Dir
Address
Address
2302
42303
R/W
2303
42304
R/W
2304
42305
R/W
2305
42306
R/W
Config
Name
Parameter
Light Group 1
302
allow dimming
Light Group 1
303
min level
Light Group 1
304
max level
Light Group 1
305
max Scene No
Unit
Range
0: only on/off
enum
control
1: allow dimming
%
0...100%
%
0...100%
int
0-16
Default
value
1
1%
100%
4
50