k
l
m
n
Check the 'HMI BGM Adjust' box to disable is volume controls buttons on the Mains Powered DAU door.
o
From the drop down list select the appropriate number to correspond with the number of End-of Lines
fitted to each speaker circuit. For each of the two speaker circuits of the Mains Powered DAU at least 1
End-of Line (EOL) 10KW resistor is required for correct monitoring and a maximum of up to 4 EOLs can
be fitted to a speaker circuit. Normally there is only 1 EOL required at the end of a speaker circuit. If
there are spur circuits or there is a requirement to monitor partial break on a speaker wiring, then there
could be up to 4 EOLs fitted to a speaker circuit.
p
Select the routing of PA audio to be via the 'Audio Loop'. The routing of audio via 'PA Loop' is for future
use.
24
www.acornfiresecurity.com
Uncheck the appropriate box if Public Address, Background Music, Local Audio input
and Local Microphone are being used.
Select the required Audio Pack from this list, the default Audio Pack 1.
Configure the required Audio priorities for Local message, Central
message, PA microphone, Background Music, Local Audio and Local
microphone. Note it is not possible to set the same priority for more than
one Audio.
Upon selecting a Mains Powered DAU device in the system tree you can
prioritise the audio output to speaker circuits. The auxiliary relay inside the
Mains Powered DAU can be re-configured to activate with the operation of
any combination of audios.