Honeywell GENT COMPACT-MAINS-DAU Commissioning Instructions page 19

Mains powered dau
Table of Contents

Advertisement

Steady ON
Key:
Audible
indication
(Local
Visual
Buzzer)
Indications
Speaker Circuit 1
or
amber
3 beeps
Speaker Circuit 2
+
every 5s
amber
Fault
amber
Fault
amber
3 beeps
every 5s
System Fault
+
amber
3 beeps
Fault
every 5s
amber
System Fault
+
amber
3 beeps
Fault
every 5s
amber
Fault
amber
3 beeps
every 5s
System Fault
amber
Confirmation
beep
During factory testing a link is placed across P30 o the MCB, which gives the following indication
unit when fitted on site should give such an indication then check and remove the link placed across P30, see page13
for link location.
www.acornfiresecurity.com
Flashing
Meaning
Speaker circuit End-of Line (EOL)
Mismatch Fault
For example: The number of
end-of-line units configured for a
speaker circuit off a Main DAU
during commissioning does not
match the number of end-of-line
units used on a speaker circuit.
Monitored Input 1/2/3 Fault
EEPROM Integrity Fault
(Latching fault)
Flash Integrity Fault
(Latching fault)
Audio Configuration Integrity Fault
(Latching fault)
Configuration Mode (check MCB
ACS CONFIG header P6). This
indication will have higher priority
over System Fault.
www.acornfiresecurity.com
Mains Powered DAU
Possible action(s)
¨
Disconnect the speaker circuit from
the MCB and measure the resistance
and ensure the measured value
matches the number of End-of Line
(EOL) on the speaker circuit, see page
9.
¨
Check at the Commissioning tool how
many end-of-line units were entered
for the speaker circuit. If entered value
does not match then configure the
Vigilon Compact VA panel with
correct EOL value for speaker circuit..
¨
Check the respective 'Monitored input'
circuit and rectify any open circuit or
short circuit faults.
¨
Check the configuration at the
commissioning tool for monitored
input type and ensure it has been
correctly set for either End-of-line
monitoring or Logic level monitoring.
¨
Carry out a 'Reset All Faults' action,
see page 20.
¨
If this fault indication reappears
following a number of resets then
replace the MCB.
¨
Carry out a 'Reset All Faults' action,
see page 20.
¨
If this fault indication reappears
following a number of resets then
replace the MCB.
¨
Carry out a 'Reset All Faults' action,
see page 20.
¨
Reload the configuration to the
Vigilon Compact VA panel from the
Commissioning tool as there is an
integrity issue with the internal audio
configuration.
¨
Indicates that the Mains Powered DAU
is in configuration mode Link P6 on
MCB is in ENABLE position.
Ensure on completion of
commissioning the jumper is placed in
DISABLE position and the System
Fault LED is not flashing.
green
Power
. If the
19