How To Interpret Indications And Take Actions - Honeywell GENT COMPACT-MAINS-DAU Commissioning Instructions

Mains powered dau
Table of Contents

Advertisement

How to interpret indications and take actions

Steady ON
Key:
Audible
indication
(Local
Visual
Buzzer)
Indications
Power
green
VA Activated
red
System Fault
amber
Continuous
Fault
amber
Comms Fault
amber
3 beeps
Fault
every 5s
amber
Comms Fault
amber
3 beeps
VA Activated
every 5s
red
System Fault
amber
Fault
amber
Power Fault
amber
3 beeps
System Fault
every 5s
amber
Fault
amber
Power Fault
amber
3 beeps
Fault
every 5s
amber
Message Fault
amber
3 beeps
System Fault
every 5s
amber
Fault
amber
www.acornfiresecurity.com
Flashing
Meaning
Normal Quiescent State - with no
faults present
Voice Alarm Activated
System Fault
(Latching fault)
Vigilon Audio Fallback Mode
Vigilon Driver Communications
Fault
(Latching fault)
Power Supply Communications Fault
(Latching fault)
Power Supply Mains / DC Rails /
Internal / Battery / Charger Fault
Message Store Communications /
Message Lengths Fault
(Latching fault)
www.acornfiresecurity.com
Mains Powered DAU
Possible action(s)
-
-
¨
Carry out a 'Reset All Faults' action,
see page 20.
¨
If this fault indication reappears
following 3 resets then replace the
MCB.
¨
Check communications and wiring to
the Vigilon Compact VA panel.
Indication that vigilon driver draws
power from the audio loop and not
from the device loop.
¨
Check communications and wiring to
the Vigilon Compact VA panel.
Carry out a 'Reset All Faults' action,
see page 20.
If this fault indication reappears
following a number of resets then
replace the MCB.
¨
Check the wiring between PSU and
MCB.
¨
Carry out a 'Reset All Faults' action,
see page 20.
If this fault indication reappears
following a number of resets then
replace the PSU and if the problem
persists replace the MCB.
¨
Check Mains supply is switched On.
Check the general condition of the
battery and replace if it is at the end of
life. Check mains and battery fuses.
Carry out a 'Reset All Faults' action,
see page 20.
¨
If this fault indication reappears
following a number of resets then
replace the PSU.
¨
Power Down the Mains Powered DAU
and then Power Up.
¨
If this fault indication reappears
following a number of Power Down &
Power Up then firstly replace the
Message Store Card and if the
problem persists then replace the
MCB.