Xls-Rel Indications On Xls1000 Panels - Honeywell XLS-REL Technical Reference Manual

Releasing module
Table of Contents

Advertisement

XLS-REL trouble indications

XLS-REL indications on XLS1000 panels

Table 4-2: Releasing Module indications
Device
Condition
Abort
Short
Open
Manual
Short
Open
Prerelease_1
Short
Open
Prerelease_2
Short
Open
Abort
No riser
Manual
Prerelease_1
Prerelease_2
Release_1
Release_2
4.4
Warning! Disconnect all wiring on TB4 of the XLS-REL
(release circuits 1 and 2) during system service. Disabled points
will not prevent activation of the release circuits. Failure to
follow these instructions may result in loss of life, serious injury,
or property damage.
When programming is complete, the fire alarm control panel will
reset itself, reconstruct the line datacard, and map it. Upon reset,
device supervision may cause the panel to generate a common
trouble active for each XLS-REL circuit. This is a normal
indication, and it should go away within minutes. Table 4-2 lists
the indications you may see for the XLS-REL on the 3-LCD.
LED
3-LCD message
Monitor
MONITOR ACT (Abort)
Trouble
COMMON TRBL ACT
Abort*
Expanded message: TROUBLE OPEN ACT
Alarm
PULL STATION ACT
Manual*
Trouble
COMMON TRBL ACT
Manual*
Expanded message: TROUBLE OPEN ACT
Trouble
COMMON TRBL ACT
Prerelease_1*
Expanded message: TROUBLE SHRT ACT
Trouble
COMMON TRBL ACT
Prerelease_1*
Expanded message: TROUBLE OPEN ACT
Trouble
COMMON TRBL ACT
Prerelease_2*
Expanded message: TROUBLE SHRT ACT
Trouble
COMMON TRBL ACT
Prerelease_2*
Expanded message: TROUBLE OPEN ACT
Trouble
COMMON TRBL ACT
Device (Abort, Manual, Prerelease_1, Prerelease_2,
Release_1, or Release_2)*
Expanded message: INTRNL TRBL ACT
XLS-REL Technical Reference Manual