Burner control units BCU 460, BCU 465 Technical Information · GB 6 Edition 11.19 • For burners in intermittent operation or in continuous operation • Flame control by UV, ionization or a further option of using the furnace chamber temperature •...
▼ It can be used for directly ignited industrial burners of unlimited capacity. The burners may be modulating- controlled or stage-controlled. Installation in the imme- BCU 460, BCU 465 · Edition 11.19...
Page 7
If necessary, the device parameters can be adjusted easily using BCSoft. All valid parameters are saved on an integrated param- eter chip card. The parameter chip card can be removed BCU 460, BCU 465 · Edition 11.19...
The gas/air mixture is adjusted to the requirements of the applications using the parameters of pre-ventila- tion and post-ventilation. The pressure switch moni- tors the air flow in the air supply line or in the flue gas exhaust. BCU 460, BCU 465 · Edition 11.19...
Control signals that are relevant for safety, such as the safety interlocks, purge and HT input, are wired inde- pendently of the bus communication using separate cables. BCU 460, BCU 465 · Edition 11.19...
BCU and the butterfly valve BVA is set to the pre-purge position. In the event of a temperature demand, the burner con- trol unit BCU activates input DI 1 via the output at ter- BCU 460, BCU 465 · Edition 11.19...
DI 2 is activated via the air valve output of the BCU and the butterfly valve BVA is set to the pre-purge position. In the event of a temperature demand, the burner con- trol unit BCU activates input DI 1 via the output at ter- BCU 460, BCU 465 · Edition 11.19...
VAS 1 VR..L Control: ON/OFF or High/Low The BCU provides the cooling and purging processes. Parameter A078 = 4 is selected so that the two-stage burner starts at low-fire rate. When the operating state BCU 460, BCU 465 · Edition 11.19...
Optional: the pressure switch monitors the air flow during pre-purge and operation. The gas/air mixture is adjusted to the requirements of the application using the parameters of pre-ventilation and post-ventilation. BCU 460, BCU 465 · Edition 11.19...
HT output that the furnace system is in High temperature mode (HT). When the HT input is activated, the burner control units switch to High temperature mode. They operate without evaluat- BCU 460, BCU 465 · Edition 11.19...
In addition, air/gas ratio monitor- ing for the zone or the furnace is required. As soon as the safety temperature monitor STM signals a furnace temperature of ≥ 850°C (1562°F), the burner BCU 460, BCU 465 · Edition 11.19...
In this type of control, >750° LM..F3 the burner output pulse frequency FCU 500..F0 always maintains full momentum 47 48 and results in maximum convection Purge in the furnace chamber, even with regulated heating. ▼ VR..L BCU 460, BCU 465 · Edition 11.19...
Page 17
ϑ VR..L test, flow detector and pressure µC BCU 460/ switch check (gas , gas min. max. >750° LM..F3 ) are provided by the FCU 500. FCU 500..F0 min. 47 48 Purge VR..L BCU 460, BCU 465 · Edition 11.19...
LDS outputs on the FCU and the corresponding in- puts on the BCUs ensures that the burners can only start if the safety interlocks and the LDS output have enabled burner start-up. BCU 460, BCU 465 · Edition 11.19...
– (EU) 2016/426 (GAR), Gas Appliances Regulation – EN 13611:2015+AC:2016 – EN 1854:2010, class S FM approved Factory Mutual (FM) Research Class: 7610 “Combus- tion Safeguards and Flame Sensing Systems”. Suitable for applications pursuant to NFPA 86. www.approvalguide.com BCU 460, BCU 465 · Edition 11.19...
BCU type label Power module, replaceable Power module type label Parameter chip card (PCC), replaceable Bus module, replaceable M5 screw terminal for burner ground There are two control keys for the control unit: BCU 460, BCU 465 · Edition 11.19...
Connection for sensor 2 with pilot lamp to monitor the air pressure (AC mains voltage) Connection for the sensor of the valve proving system (tightness control pressure switch or POC switch for checking the closed position) 59, 38 Valve proving system ▼ BCU 460, BCU 465 · Edition 11.19...
Page 29
Contact between terminals 95 and 97 closes once the operating signal has been received 96, 97 Floating contact from burner 2. Parameter-dependent function Contact can be adjusted depending on parameter I054 86, 87 90, 91 Parameter-dependent function Contact can be adjusted depending on parameter I051 BCU 460, BCU 465 · Edition 11.19...
Safety time 1 t (A094) running, ignition in process, valves for 1 gas stage open and min. operating time starts to elapse (A061) ▼ If no flame detected: max. 3 start-up attempts (A007) or fault lock-out BCU 460, BCU 465 · Edition 11.19...
Pre-ventilation time after safety shut-down running (A036) ▼ In the event of flame failure: pre-purge running restart or fault lock-out ▼ Min. pause time running again (parameter A062) ▼ Flame simulation check (if parameter A003 = 1) ▼ ▼ BCU 460, BCU 465 · Edition 11.19...
Page 32
If min. operating time t has elapsed: operation signalling contact opens, gas valves close and running time (A042) starts to elapse ▼ Over-run time (post-ventilation) t running (A039) Air actuator is closed, running time starts to elapse (A042) BCU 460, BCU 465 · Edition 11.19...
As soon as there is a purge signal at terminal 3 of BCU, page 93 (Air actuator control). the control element is activated by the outputs for ca- pacity control to approach the position for pre-purge. BCU 460, BCU 465 · Edition 11.19...
As soon as there is a purge signal at terminal 3 of BCU.. F3, the air valve is activated by the output at terminal 65. The protective system (FCU 500) starts the pre- purge time if there is adequate air flow. After the elapse BCU 460, BCU 465 · Edition 11.19...
Burners BIC..M are tailored to the appropriate capacity and combined with tapered IC 40 + BVH ceramic tubes (TSC..M). ▼ BCU 460, BCU 465 · Edition 11.19...
Page 37
For further information on burner BIC..M, see www.docuthek.com Gas and air are supplied via the same connections as in Flame mode. No ignition takes place in the burner tube. BCU 460, BCU 465 · Edition 11.19...
850°C is required for flameless operation. Flameless mode is enabled via the input at terminal 7: depending on parameter A064, the system is either switched over immediately or the next time the BCU 460, BCU 465 · Edition 11.19...
Page 39
Hot air compensation and ratio control are not the re- sponsibility of the BCU . These functions must satisfy the requirements of a protective system pursuant to EN 746-2 and be implemented externally. BCU 460, BCU 465 · Edition 11.19...
1200 kW (NFPA 86: from 117 kW or 400,000 Btu/h). The tightness control function satisfies the require- ments of EN 1643 (Valve proving systems for automat- ic shut-off valves for gas burners and gas appliances). BCU 460, BCU 465 · Edition 11.19...
This ensures µC that the test volume V can be vented during the tight- ness test with the air/gas ratio control closed. 36 37 BCU 460, BCU 465 · Edition 11.19...
V2 is around atmospheric pres- – p Z > p Z > sure and the volume downstream of V2 is at least 5 × – higher than the volume between the valves. ▼ BCU 460, BCU 465 · Edition 11.19...
Page 43
V2 is at least 5 × higher than the volume between the valves. t L = A059 t L = A059 t M = A056 t M = A056 – p Z > p Z > – BCU 460, BCU 465 · Edition 11.19...
3 s for the tightness test if the main gas valves are actuated directly. If gas can flow into the combus- tion chamber when a valve is opened, the gas volume must not exceed 0.083% of the maximum flow rate. BCU 460, BCU 465 · Edition 11.19...
Adjustable using parameter A056 2 x p [s] = For a large test volume V with reduced testing time Adjustable using parameter A056 0.9 x p [s] = Conversion into US units, see page 136 (Converting units) BCU 460, BCU 465 · Edition 11.19...
By checking the closed position using the proof of clo- >750° sure function, the BCU complies with the requirements BCU 46x..C1 of NFPA 85 (Boiler and Combustion Systems Hazards Code) and NFPA 86 (Standard for Ovens and Furnaces). BCU 460, BCU 465 · Edition 11.19...
In the event of faults or service interventions, details on troubleshooting can be derived from the device statistics and the fault history. BCU 460, BCU 465 · Edition 11.19...
PROFINET The basic function of fieldbus communication is the exchange of process and required data between a con- troller (e.g. a PLC) and several distributed devices (e.g. BCM with BCU). BCU 460, BCU 465 · Edition 11.19...
For information on planning and the structure of a net- work and the components to be used (e.g. cables, lines and switches) for PROFINET and PROFIBUS, see www.profibus.com, for EtherNet/IP, see www.odva.org. BCU 460, BCU 465 · Edition 11.19...
The GSD/EDS file for the bus module can be obtained from www.docuthek.com. The steps required to integrate the file are described in the instructions for the engineering tool for your automation system. BCU 460, BCU 465 · Edition 11.19...
Outputs (PLC ➔ BCU) Burner 1 flame signal Burner 2 flame signal Status signal Fault and warning signals Remaining times Temperature Input information (via terminal and bus) Output information (via terminal and bus) ▼ BCU 460, BCU 465 · Edition 11.19...
Page 54
Terminals 1 to 41 (dependent on parameters I061 to I074) can be wired parallel to the bus communication. This allows the BCU to be controlled using the digital signals of the bus communication or the inputs at the terminals. BCU 460, BCU 465 · Edition 11.19...
Page 55
The flame signal occupies one byte with values from 0 to 255 (= flame signal from 0 to 25.5 µA). Bit Byte n Data type Format Value 0 – 255 Burner 2 flame signal Byte (0 – 25.5 μA) See code tables “BusCommunication_BCU4_R2.xlsx” at www. docuthek.com. BCU 460, BCU 465 · Edition 11.19...
Page 56
Byte n+3 Data type Format Value Bit Byte n Byte n+1 Data type Format Value Warning signals Word 0 – 655535 0 – 6554 Temperature Word (0 – 6554 K) See code tables “BusCommunication_BCU4_R2.xlsx” at www. docuthek.com. ▼ BCU 460, BCU 465 · Edition 11.19...
Page 57
BOOL Terminal 66 Free Free BCU ON Burner 1 flame Free BOOL Terminal 67 Free Free Manual mode Burner 2 flame Free BOOL 1) Only with BCU 465 depending on the parameter settings. BCU 460, BCU 465 · Edition 11.19...
Operator statistics, extreme values 1011 Operator statistics, time counters The available data records differ in terms of their indexes. The contents and description of the indexes are described in the code table “BusCommunication_BCU4_R2.xlsx” (download from www.docuthek.com). BCU 460, BCU 465 · Edition 11.19...
The specified ranges relate to bus cable type A (2-core, Byte 0 shielded and twisted), e.g. Reset Siemens, Order No. 6XV1830-0EH10, or Start 1 Lapp cable unitronic, Order No. 2170-220T. Cooling Purge Free Free Free Free BCU 460, BCU 465 · Edition 11.19...
Burner 1 operation/controller enable (with air) Over-run up to minimum capacity Post-purge Data transfer (programming mode) – – Device Off In Manual mode, four dots flash on the display. Air actuator (control element/valve) is open. BCU 460, BCU 465 · Edition 11.19...
E 40 Inlet valve(s) leaking Leak found on inlet valve E 41 Outlet valve(s) leaking Leak found on outlet valve E 44 Pressure switch/gas valve wiring E 45 Gas valve wiring Reversed valve connection BCU 460, BCU 465 · Edition 11.19...
Page 62
Fault Air monitor “no flow” state check. The signal from the Air monitor “no flow” state pressure switches is received at terminal 36 or 37 before the air actuator is opened. Low air pressure Fault Air monitor operating check BCU 460, BCU 465 · Edition 11.19...
Page 63
Flame failure during flame proving period 1 while air actuator is E A3 Flame failure during flame proving period 1 open E A4 Flame failure during burner 1 operation Flame failure during burner 1 operation while air actuator is open BCU 460, BCU 465 · Edition 11.19...
Time in seconds Pre-ventilation/flameless A028 0 – 250 Time in seconds Pre-purge time tPV A034 0 – 6000 Time in seconds 6000 Pre-ventilation time tVL A036 0 – 250 Time in seconds Over-run time tNL A039 0 – 60 Time in seconds BCU 460, BCU 465 · Edition 11.19...
Page 65
2 – 25 Time in seconds Proof of closure function test period A060 0 – 6000 Time in seconds Minimum operating time tB A061 0 – 250 Time in seconds Minimum pause time tMP A062 0 – 3600 Time in seconds BCU 460, BCU 465 · Edition 11.19...
Page 66
Via fail-safe bus (K-SafetyLink) Safety interlocks (bus) A085 Via terminal Via fail-safe bus (K-SafetyLink) and terminal Via fail-safe bus (K-SafetyLink) Purge (bus) A087 Via terminal Via non-fail-safe bus Via fail-safe bus (K-SafetyLink) or terminal BCU 460, BCU 465 · Edition 11.19...
Page 67
POC V2 POC V3 POC V4 POC V5 GPS Flame mode GPS Flameless operation GPS Operation Function of sensor 2 A102 See A101 See A101 Function of sensor 3 A103 See A101 See A101 BCU 460, BCU 465 · Edition 11.19...
Page 68
A129 Flue gas Air actuator & flue gas Cooling air & flue gas Air actuator & cooling air & flue gas Over-run time, flameless tNL A139 0 – 60 s Time in seconds BCU 460, BCU 465 · Edition 11.19...
Cooling air valve Flue gas valve Fault signal Burner 1 operating signal Ready signal Air signal Purge signal Contact 90, 91/92 function I051* Cooling air valve Flue gas valve Fault signal Burner 1 operating signal BCU 460, BCU 465 · Edition 11.19...
Page 70
Air actuator R1 Air actuator R2 Function of input 1 I061* Start 1 Reset Purge LDS start-up conditions High temperature operation Flameless operation Auxiliary gas Function of input 2 I062* See I061 See I061 BCU 460, BCU 465 · Edition 11.19...
Page 71
I073* See I061 See I061 Function of input 41 I074* See I061 See I061 * Interface parameters I040 to I099 are set at the factory and normally do not need to be adjusted. BCU 460, BCU 465 · Edition 11.19...
The BCU indicates when the mains switch has been switched off. The parameters cannot be scanned when the BCU is switched off or when a fault or warning is displayed. BCU 460, BCU 465 · Edition 11.19...
The flame simulation check is conducted after ap- ϑ Start 1 plying the start-up signal (start 1) during the waiting time t t LV The flame simulation check of the burner is always ac- tive until valve V1 is enabled. BCU 460, BCU 465 · Edition 11.19...
The safety function of the device’s internal flame con- trol system is deactivated . In High temperature mode, the gas valves are opened and the burners are started as usual without monitor- ing the presence of a flame. ▼ BCU 460, BCU 465 · Edition 11.19...
Page 76
UV control with UVC). ▼ If the temperature in the furnace chamber drops below 750°C, the HT input must be disconnected from the electrical power supply and the furnace must then be operated with flame control. BCU 460, BCU 465 · Edition 11.19...
Page 77
(recommended in the case of UV control with UVS). If no flame signal is present when High temperature mode is deactivated, the burner control unit performs a fault lock-out, regardless of parameter A006. E 04 ϑ BCU 460, BCU 465 · Edition 11.19...
BCU safety shut- down with subsequent fault lock-out. The fault mes- sage E 04 will flash in the BCU display depending on the burner operating mode. BCU 460, BCU 465 · Edition 11.19...
Parameter A078 = 1: burner 1 with pilot gas. Three valves (V1, V2 and V3) are included for a burner with a pilot gas valve. These are connected to the valve out- puts (terminals 60, 61 and 62). Valves V1 and V3 open BCU 460, BCU 465 · Edition 11.19...
Page 80
After the flame proving period t elapsed, valve V2 opens to enable the 2 gas stage. If a previous version is replaced by the BCU 4, param- eter A078 = 4 must be selected in any event. ▼ BCU 460, BCU 465 · Edition 11.19...
Page 81
In Flame mode (< 850°C), the burner is started con- On/Off burner operation with different gas paths in ventionally with the pre-ventilation time t defined in Flame mode and Flameless mode. parameter A036. Process Control (PCC) ϑ BCU 465..F3 ▼ µC VR..N BCU 460, BCU 465 · Edition 11.19...
Page 82
. The gas valves V1 and V3 are opened at the start of the safety time t ϑ The air pressure switch and the position of the IC are checked via terminal 36 on the BCU. BCU 460, BCU 465 · Edition 11.19...
Safety time 1 must be determined on the basis of cur- rent national standards and regulations . The burner application and the burner capacity are the main cri- teria for this . BCU 460, BCU 465 · Edition 11.19...
The precondition for an automatic restart is that the burner can restart (as intended in all operating phases). In this case, it must be ensured that the program se- quence started by the BCU matches the application. BCU 460, BCU 465 · Edition 11.19...
The BCU has a safety shut-down with subsequent fault lock-out option if more than 5 restarts are performed within a period of 15 minutes. BCU 460, BCU 465 · Edition 11.19...
Parameter A077 = 3: operation. In Flame and Flameless mode, valve V4 is opened as long as the auxiliary gas signal is received at one of the terminals and the BCU is operating. BCU 460, BCU 465 · Edition 11.19...
BCU initiates a reaction depend- ing on the parameter setting. When the air actuator is switched off, the “no flow” state (default position) of the air pressure switch (PDZ) is checked. BCU 460, BCU 465 · Edition 11.19...
In accordance with EN 746-2, the safety time of the in- stallation during operation (total closing time) must not exceed 3 s. Under NFPA 86, section 8.10.3*, the maximum flame failure response time shall be ≤ 4 s. BCU 460, BCU 465 · Edition 11.19...
Parameter setting for this example sequence: tuator has reached the purge position. A048 = 1; A036 > 0, see also page 87 (Delayed low air pressure protection). The gas valve does not open until the pressure switch has switched. BCU 460, BCU 465 · Edition 11.19...
250 s. When the position has been reached, the BCU will initiate the next program step. Parameter A041 = 1: On; for approaching the positions for minimum/maximum capacity. The running time set using parameter A042 is activated for approaching BCU 460, BCU 465 · Edition 11.19...
Parameter A043 = 1: Post-ventilation (with BCU/LM..F1 only). The gas supply will be closed. Air continues to be supplied for the programmed duration depending on parameter A039 (in Flame mode) or A139 (in Flameless mode). ▼ BCU 460, BCU 465 · Edition 11.19...
Page 92
Parameter A043 = 3: low fire over-run, time-bound. BCU 460..F3 µC VR..L The burners are initially powered down to low-fire rate and remain in operation for the programmed duration depending on parameter A039 (Flame mode) or A139 BCU 460, BCU 465 · Edition 11.19...
(Two-stage-controlled burner). In this case, activation of the air actuator during burner start via the input at terminal 4 must be prevented. External control allows switchover between low fire and high fire during operation. ▼ BCU 460, BCU 465 · Edition 11.19...
Page 94
The air actuator opens at the same time as the first gas stage (with V1). Parameter A048 = 2: opens with gas stage 2 (operating fuel flow rate). ϑ ∨ 66 The air actuator opens simultaneously with the second gas stage/operating signal. BCU 460, BCU 465 · Edition 11.19...
Parameter A049 = 1: can be activated externally. 00 A000 ϑ ∨ 66 The air actuator can be activated externally via the input at terminal 4 during start-up. Parameter A048 must be BCU 460, BCU 465 · Edition 11.19...
Parameter setting for this example sequence: A074 = 1; A016 = 0, see also page 87 (Delayed low air pressure protection). The gas valve does not open until the pressure switch has switched. BCU 460, BCU 465 · Edition 11.19...
Flameless mode input (termi- nal 7), the burner in Flame mode is switched straight to Flameless mode. Any burner start-up will not be contin- ued until the end of the minimum operating time. BCU 460, BCU 465 · Edition 11.19...
To switch to Flameless mode, the µC HT signal from the STM (terminal 6) and the signal for Flameless mode (FLO) must be supplied to the BCU by VR..N a separate control unit (terminal 7). ▼ BCU 460, BCU 465 · Edition 11.19...
Parameter A074 = 2: High temperature operation with- out ignition. If the BCU is in High temperature mode, the ignition (ignition transformer) will not be activated for the start-up. BCU 460, BCU 465 · Edition 11.19...
An additional bypass valve must be installed in gas sec- tions with an air/gas ratio control. This valve allows the closed air/gas ratio control to be bypassed during the tightness test. BCU 460, BCU 465 · Edition 11.19...
= 3 s is inadequate (e.g. if slow opening valves are used) to fill the test volume or re- duce the pressure between the valves, bypass valves can be used instead of the main valves. BCU 460, BCU 465 · Edition 11.19...
Reset/Information button. Each time the button is pressed again, the BCU moves to the next step of the program sequence and stops there, for example for adjusting an actuator or the gas/air mix- ture. BCU 460, BCU 465 · Edition 11.19...
V3 Is monitored by the POC. Parameter A101 = 51: proof of closure function V4. The closed position of valve V4 Is monitored by the POC. Parameter A101 = 52: proof of closure function V5. The BCU 460, BCU 465 · Edition 11.19...
POC switch. If a signal is still being received from the POC switch at terminal 36, 37 or 38 after the set testing time, the BCU performs a fault lock-out with fault message “E c8”. BCU 460, BCU 465 · Edition 11.19...
(xxx = address in the range 001 parameter A081. to FEF). Parameter A081 = 0: Off. No data exchange takes place via K-SafetyLink. Parameter A082 = 1: On. Data exchange via K-Safe- tyLink is enabled. The FCU must support this function. BCU 460, BCU 465 · Edition 11.19...
High temperature mode is received. Parameter A088 = 0: Off Parameter A088 = 1: via fail-safe bus Parameter A088 = 2: via terminal Parameter A088 = 5: via fail-safe bus and terminal BCU 460, BCU 465 · Edition 11.19...
Depending on the parameterization, the burner is started with or without pre-purge. This pro- cess is controlled independently by the BCU and there- BCU 460, BCU 465 · Edition 11.19...
40 41 56 26 64 65 66 67 22 21 20 19 18 16 15 14 12 11 10 The positions for maximum capacity and ignition capacity can be set using the actuator. Terminal 41 BCU 460, BCU 465 · Edition 11.19...
Page 110
Butterfly valve position Closed Closed Closed Closed Ignition Minimum/Ignition capacity Ignition Minimum/Ignition capacity Any position between minimum and 0 – 20 mA High-fire rate High-fire rate maximum capacity Purge Maximum capacity Purge Maximum capacity ▼ BCU 460, BCU 465 · Edition 11.19...
Page 111
(Run- ning time). Parameter A041 (Running time selection) must be set to 1 to adjust this behaviour. BCU 460, BCU 465 · Edition 11.19...
LM..F3 is used. Parameter I040 = 3: bus output 1. The output at termi- nal 64 can be actuated using a bus system. Can only be selected with power module LM..F3. BCU 460, BCU 465 · Edition 11.19...
Parameter I050 = 6: fault signal. The contact is closed if a fault lock-out is active. Parameter I050 = 7: Burner 1 operating signal. The con- tact is closed if burner 1 is in operation. BCU 460, BCU 465 · Edition 11.19...
HT input is activated. It operates without eval- through the input. uating the flame signal and its internal flame control Parameter I061 = 6: cooling air. The BCU receives the system is non-functional. BCU 460, BCU 465 · Edition 11.19...
For all other parameter values and descriptions, see (Function of input 1). page 114 (Function of input 1). 11 .16 .5 Function of input 5 Parameter I065 To define the input signal for terminal 5. BCU 460, BCU 465 · Edition 11.19...
(Function of input 1). 11 .16 .11 Function of input 38 Parameter I071 To define the input signal for terminal 38. A sensor may be connected to this input (I071 = 1, 2 or 3) if necessary. BCU 460, BCU 465 · Edition 11.19...
Replacement possibilities 12 Replacement possibilities Burner control units BCU 460 and BCU 465 can be replaced by the next-generation devices BCU 460 and BCU 465. By comparison to the previous generation, the next-generation BCU 4 units feature new technologies and func- tions which can be freely parameterized.
Page 118
When making the replacement, check whether the additional sub-distribution board is still required. 4) If power management is implemented using the safety interlocks, this specification is omitted. Power management via phase (L1) = E1. BCU 460, BCU 465 · Edition 11.19...
Optional outputs: none not fail-safe fail-safe Energy supply: via safety interlocks via L1 No connection plugs* Connection plugs for the power module are supplied with the BCU..K1 and BCU..K2. BCU 460, BCU 465 · Edition 11.19...
Securing the device from inside ards. Screw on the BCU with four screws, Ø 4 mm, min. length 15 mm. Securing the device from outside The unit remains closed. BCU 460, BCU 465 · Edition 11.19...
(AWG 12), for spring force terminals max. 1.5 mm (AWG 16). Do not route BCU cables in the same cable duct as frequency converter cables or cables emitting strong fields. External electrical interference must be avoided. BCU 460, BCU 465 · Edition 11.19...
FCU and BCU. The data transfer can be enabled using parameter A081. The FCU must support the function for communicating via K-SafetyLink. BCU 460, BCU 465 · Edition 11.19...
Order No.: 74919469 15 .4 Connection plug set For wiring the BCU. Connection plugs with screw terminals, Order No.: 74924876. Connection plugs with spring force terminals, 2 con- nection options per terminal, Order No.: 74924877. BCU 460, BCU 465 · Edition 11.19...
With boreholes for conduit 74960712 connections (BCU..P7) 1) Recommended for PROFINET or Ethernet. 2) Recommended for replacement of a previous version of the 74960706 BCU for PROFIBUS. The PROFIBUS plug is identical. 74960712 74960707 74960709 74960711 BCU 460, BCU 465 · Edition 11.19...
▼ and heating during operation from the automation system (PLC) to the BCM. In the opposite direction, it BCU 460, BCU 465 · Edition 11.19...
Page 130
The power supply for the bus terminator is provided by the BCU. The bus terminator can be activated in the PROFIBUS plug connector. Ensure there is an equipotential bond between the de- vices. BCU 460, BCU 465 · Edition 11.19...
BCSoft. BCM..S1 can only be commissioned us- ing BCSoft. Check the code switch settings (001 to 125) on the BCM for PROFIBUS communication between BCSoft and the control unit. BCU 460, BCU 465 · Edition 11.19...
Installation location: min. IP 65 (for installation in Two RJ45 sockets – BCU 4xx). Three-point step control via bus Permitted operating altitude: < 2000 m AMSL. Order No.: 74960690 Order No.: 74960691 Order No.: 74960692 BCU 460, BCU 465 · Edition 11.19...
▼ Ignition transformer (terminal 51): max. 2 A. Total current for the simultaneous activation of the valve outputs (terminals 60, 61, 62, 63 and 64) and of the ignition transformer (terminal 51), protected by F1/ F2: max. 2.5 A. BCU 460, BCU 465 · Edition 11.19...
Safety Integrity Level (SIL) MTTF Safe failure fraction SFF 99.0% – Max. service life under operating conditions: 10 years after date of production. For a glossary of terms, see page 141 (Glossary). BCU 460, BCU 465 · Edition 11.19...
In the case of communication errors, all This corresponds to the safety time during operation signals are interpreted as inactive. and can be parameterized to between 1 and 4 s. Safety-relevant data are transmitted on the basis of the black channel principle. BCU 460, BCU 465 · Edition 11.19...
20 .4 SIL and PL for BCU 4 SIL Safety Integrity Level/PL Performance Level See page 136 (Safety-specific characteristic values for SIL and PL). BCU 460, BCU 465 · Edition 11.19...
Order No. for the power module, see type label: The device and user statistics can be displayed using the engineering tool BCSoft for further diagnostics and troubleshooting. The user statistics can be reset using engineering tool BCSoft. BCU 460, BCU 465 · Edition 11.19...
Input for high temperature operation Pressure switch for tightness control (TC) Pressure switch for maximum pressure Pressure switch for minimum pressure Differential pressure switch Actuator with butterfly valve TC Tightness control /2 Half of the inlet pressure BCU 460, BCU 465 · Edition 11.19...
1, 2, 3 or 6 s (depending on safety for the use of the application, e.g. safety temperature time t selected). limiter, minimum/maximum gas pressure) must isolate input from the voltage supply. BCU 460, BCU 465 · Edition 11.19...
(Fault signalling). The gas valves are disconnected from the electrical power supply. The fault signalling contact opens if the mains voltage fails. BCU 460, BCU 465 · Edition 11.19...
23 .13 Diagnostic coverage DC Measure of the effectiveness of diagnostics, which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failures BCU 460, BCU 465 · Edition 11.19...
Unit: 1/h. from EN 13611/A2:2011 23 .16 Mean time to dangerous failure MTTF Expectation of the mean time to dangerous failure from EN ISO 13849-1:2008 BCU 460, BCU 465 · Edition 11.19...