Honeywell XLS-REL Technical Reference Manual page 24

Releasing module
Table of Contents

Advertisement

Installing the XLS-REL
[11]
Manual release circuit [5]
Class A
Signature
Data
Circuit
+
_
In
+
Out
_
[1]
[2]
[7]
[8]
Release
circuit 1
RELA-EOL
1
2
3
[6]
4
RELA-EOL
1
2
3
[6]
4
RELA-EOL
1
2
3
[6]
4
RELA-EOL
1
2
3
[6]
4
[5]
Figure 1-8: XLS-REL wiring
1.16
[3]
[4]
[5]
[8]
1
2
3
4
TB3
TB1
4
3
2
1
Releasing Module
TB4
1
2
3
4
_
_
+
+
[1]
[2]
[7]
[8]
[10]
[10]
[11]
[11]
Release
circuit 2
RELA-EOL
1
2
3
[6]
4
RELA-EOL
1
2
3
[6]
4
RELA-EOL
1
2
3
[6]
4
RELA-EOL
1
2
3
[6]
4
[5]
Abort circuit
[11]
First alarm output
TB6
4
1
2
3
3
TB2
2
1
TB5
1
2
3
4
_
_
+
+
Prerelease circuit 2
(steady)
Prerelease circuit 1
(pulsed 15/60/Steady)
Notes
[1]
Four RELA-EOLs per circuit, max.
[2]
Class B, 24 Vdc output
[3]
Class B, normally-open manual release station
[4]
Class B, normally-open abort station
W
[5]
Listed 47 k EOL resistor
[6]
Listed 24 Vdc n
onpolarized valve. The releasing
solenoid
valve wiring is not supervised for wire-
to-wire shorts. Run the connection to the valve
in conduit within 20 feet of the RELA-EOL
Solenoid Polarizing Relay.
[7]
Polarity of circuit shown in supervisory state. On
alarm, polarity reverses.
[8]
Supervised and power-limited.
[9]
P
ower-limited when connected to a power-
limited source. If nonpower-limited, maintain 1/4
inch (6.4 mm) separation. Otherwise, use FPL,
FPLR, or FPLP in accordance with the National
Electric Code (NEC). Destroy power-limited
markings.
[10] Listed service disconnect station
[11] Not included in preaction or deluge sprinkler
systems
[12] Ten Releasing Modules per loop, max.
13
Installations, which include other wiring, require
FPL, FPLR, FPLP, or equivalent NEC-approved
wiring for all power-limited wiring.
XLS-REL Technical Reference Manual
RELEASE023.CDR