General / Application - Honeywell Esser RZT 8000 Installation Instruction

Refurbishment zone transponder
Table of Contents

Advertisement

Available languages

Available languages

Refurbishment Zone Transponder RZT 8000
1

General / Application

The third-party detector connecting module RZT 8000 (Refurbishment Zone Transponder) Part No. 80863x.10,
is used – in the same way as an esserbus
esserbus
®
-PLus of the ESSER fire alarm control panels (FACPs). Service and programming software tools
8000 are used for programming.
®
Up to 100 esserbus
transponders / third-party detector connecting module can be connected to one fire alarm
control panel. Up to 1.000 different control zones (e.g. relays) can be programmed in a FACP with the
programming software tools 8000.
In case of a malfunction (short circuit), the optional zone isolator (Part No. 788612) disconnects the zone
between two isolators. This does not affect the function of the other devices. Power for third-party detector
connecting modules is supplied via the FACP or external power supply. Two versions of the third-party
connecting module are available for connecting individual automatic fire detectors and manual control points
from other manufacturers.
Refurbishment Zone Transponder RZT 8000 (24 V DC)
Refurbishment Zone Transponder RZT 8000 (12 V DC)
The modules can be connected to the following ESSER fire alarm control panels, taking the system limits into
consideration:
FACP FlexES Control
FACP IQ8Control
FACP Compact
An overview of the RZTs that can currently be connected is provided in the download area at www.esser-
systems.com. Consult with Technical Sales before connecting any other types.
System limits
Max. 100 RZT 8000 per FACP. The total number of RZT and esserbus
connected to one control panel is restricted to 100 devices.
Up to 31 RZT 8000 can be combined into one separate zone on one loop.
Please refer to the RZT documentation during installation of the devices.
18
®
transponder – as an independent device on the esserbus
Part No. 808630.10
Part No. 808631.10
®
transponders that can be
FB 789807.10 / 05.17
®
/