Connection Of The Relay Outputs; Operating Mode 1 - Relay Monitoring - Honeywell Esser RZT 8000 Installation Instruction

Refurbishment zone transponder
Table of Contents

Advertisement

Available languages

Available languages

6

Connection of the relay outputs

Selection of the three relay operating modes is done the jumpers X10 to X15 on the board of the third-
party detector connecting module. Furthermore the relay operating mode must also be edited in the
customer data of the ESSER fire alarm control system.
Different operating modes may be used for the two relay outputs. This allows for mixed operation of a
third-party detector connecting module.
The relay outputs are protected by an electronic protecting device (Multi-Fuse). To reset this protection,
supply power must be removed from the third-party detector connecting module for a duration of approx.
30 seconds.
6.1

Operating mode 1 - relay monitoring

When a relay is activated, the internal 12 V DC supply voltage (terminal X1) is switched through to the
connected external device, e.g. on optical and/or audible signalling device.
Arrange jumpers (X10 to X15) for mode selection in to accordance with Fig.
settings for relay output 1: jumpers X10, X11, X12
settings for relay output 2: jumpers X13, X14, X15
+UB 12 V
GND
Jumper closed
Jumper open
Fig. 10 : Application example – Operating mode 1 (relay monitoring)
Max. contact load of relays K1 and K2: 30 V DC / 1 A or 48 V AC / 0.5 A
FB 789807.10 / 05.17
alarm device
F1
X1
T1,25A
+12V
BR1
0V
X7.2
Isolator
788612
X7.1
Refurbishment Zone Transponder RZT 8000
visual
1N4004
X3
BR2
K1
BARCODE
audible
alarm device
1N4004
X4
K2
23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Esser 80863x.10

Table of Contents