Disable Zone (H2/B1) - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512 v2.3.x
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
24.1
Action
"Access"
Scroll to menu H2.
"A"
"A"
Write zone number (e.g.
001)
"A"
"A"
Rev: 1

Disable zone (H2/B1)

When a whole zone is disabled, all alarm points within the zone are
disabled except the addressable manual call points.
Disabled zones are listed in menu H4/U1 from which it is also
possible to get a print-out.
Text in display
Disable or re-enable
Disable zone
Disable zone: 000
Disable zone: 001
Automatic re-enabling:0 (0=No,1=Yes)
Time: HH:MM
(Default is current time + 3 hours)
Disable zone: 000
Operating Instructions Fire alarm system EBL512 V2.3.x
ACCEPT? H2
ACCEPT? B1
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
76
Comments
According to chapter
"Access", see page 72.
Press "A" to accept.
Press "1" for aut. re-
enabling and accept or
change the time (max. 24
hours). Press "A" to
accept. LED
"Disablements" (L8) will
light up.
If more disablements shall
be done, continue like
above. If not, press
"Return" to menu B1.
Scroll or press "Return" to
menu H2. Scroll or press
"Return" to log off.