Operating Instructions Fire alarm system EBL512 V2.3.x
program area (n)"
FAULT: Comm. FBP xx, 1587-board x, CU xx
FBP=1826 / 1828.
• The contact with the ext. FBP is interrupted. Check the
cable, all connections and the 1587 board.
complete SSD downloaded (via Win512)?
address setting (1587 board / the ext. FBP), SW mode
setting, etc.
• If there is a program memory fault in the ext. FBP, there will
be a fault message in the ext. FBP display:
fault in program area (n)"
FBP will not work.
FAULT: Configuration control unit xx
Fault in the SSI = EBL512 settings downloaded from Win512.
FAULT: CU xx has no contact with CU xx
Can be shown in conjunction with new S/W download.
• Check the TLON network cable / connections.
• Faulty TLON connection board. 1590.
• No power supply to the control unit.
FAULT: CU xx has wrong information
Can be shown in conjunction with new S/W download.
One or more control units have data stored, which is not the same in
all control units. If a control unit restarts in conjunction with this
fault, a synchronization will start automatically, otherwise a
synchronization has to be started via menu H8/S10.
NOTE! It is important that all control units that are supposed to exist
(SSD downloaded via Win512) are running and are connected to the
TLON network. The TLON network programming has to be done.
FAULT: CU xx high current consumption
The control unit current consumption is > 2.5A (> 3.6A in alarm state)
and because of this, the battery charging is turned off and will be so
until the current consumption has decreased to < 2.5A (< 3.6 A) again.
FAULT: Cut-off COM-loop x, CU xx
48
(n=1 or 2). The EPU will not work.
(n=1 or 2). The ext.
Is correct /
Check the