Panasonic EBL128 User Manual
Panasonic EBL128 User Manual

Panasonic EBL128 User Manual

Fire alarm system
Hide thumbs Also See for EBL128:

Advertisement

User manual
MEW01624
Revision -
Fire alarm system
EBL128
EBL128 version 2.0.x
Daily user's manual
Author:
Jan Pettersson
Date of issue: 2013-10-18
Date of rev:

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic EBL128

  • Page 1 User manual MEW01624 Revision - Fire alarm system EBL128 EBL128 version 2.0.x Daily user's manual Author: Jan Pettersson Date of issue: 2013-10-18 Date of rev:...
  • Page 2 This page has deliberately been left blank.
  • Page 3: Table Of Contents

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Table of contents Introduction________________________________ 3 Front______________________________________ 4 Log on to the Control Unit (c.i.e.) ______________ 5 Perform monthly test (H1) ___________________ 9 Disable or re-enable (H2) ___________________ 10...
  • Page 4 Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual...
  • Page 5: Introduction

    / type "Building officer". Due to continual development and improvement different S/W versions can be found. This document is valid for EBL128 S/W version 2.0.x. (x=0 at the "Date of issue" or "Date of revision".) This document is less detailed and shorter than the Operating Instruction, MEW01623.
  • Page 6: Front

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Front Front, upper (dark grey) part. Fire Brigade Panel (FBP). Front, lower (light grey) part. Information LEDs, buttons and keypad. L1-L16 and P1-P9 refer also to the Operating Instructions, MEW01623.
  • Page 7: Log On To The Control Unit (C.i.e.)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Log on to the Control Unit (c.i.e.) User name Up to ten (10) User names (0, 1, 2 - - 9) might be programmed. Default are three User names available (0, 1 and 2) but they might have been changed and/or User names 3 –...
  • Page 8 Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Log out You will be logged out when you close the door or 60 minutes after the last action (i.e. if the key pad / push buttons have not been used for 60 min.).
  • Page 9 Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Building officer (Described in this document.) H1 Perform monthly test H2 Disable or re-enable B1 Disable zone B2 Disable zone-address B3 Disable output B4 Disable all control, ventilation, exting or interlocking outputs...
  • Page 10 Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Service personnel H1 Perform monthly test Same as Building officer but also the following menus: H5 Service A1 Calibration of superviced outputs A2 Sensitive fault detection mode...
  • Page 11: Perform Monthly Test (H1)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Perform monthly test (H1) Not available for users with access level / type "Information only".  Regarding the "Test mode" (see below) see also page 30.
  • Page 12: Disable Or Re-Enable (H2)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Disable or re-enable (H2) Not available for users with access level / type "Information only". Any disablement in the system is indicated by the LED "Disablements" (L8).
  • Page 13: Disable Zone-Address (B2)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Disable zone-address (B2) Not available for users with access level / type "Information only". Up to 100 addressable alarm points (zone-address) can be individually disabled via menu B2. Also addressable manual call points.
  • Page 14: Disable Output (B3)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Disable output (B3) Not available for users with access level / type "Information only". Up to 100 control outputs, except outputs of type "alarm device", can be individually disabled via menu B3. Disabled output will stay in (or return to) the normal condition for the output respectively.
  • Page 15: Disable All Control, Ventilation, Exting Or Interlocking Outputs

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Disable all control, ventilation, exting or interlocking outputs (B4) Not available for users with access level / type "Information only". Outputs programmed as type Control (general), type Fire ventilation,...
  • Page 16: Re-Enable Zone (B5)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Re-enable zone (B5) Not available for users with access level / type "Information only". Disabled zones are listed in menu H4/U1. Re-enabling via menu B5 has higher priority than automatic re- enabling.
  • Page 17: Re-Enable Zone-Address (B6)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Re-enable zone-address (B6) Not available for users with access level / type "Information only". Disabled alarm points (zone – address) are listed in menu H4/U1. Re-enabling via this menu has higher priority than automatic re- enabling.
  • Page 18: Re-Enable Output (B7)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Re-enable output (B7) Not available for users with access level / type "Information only". Disabled outputs are listed in menu H4/U1. If there is nothing to re-enable, --- List is empty --- will be shown.
  • Page 19: Re-Enable All Control, Ventilation, Exting Or Interlocking Outputs (B8)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Re-enable all control, ventilation, exting or interlocking outputs (B8) Not available for users with access level / type "Information only". Disabled outputs are listed in menu H4/U1.
  • Page 20: Disable / Re-Enable Alarm Devices (B9)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Disable / re-enable alarm devices (B9) Not available for users with access level / type "Information only". Disabled alarm devices are listed in menu H4/U1. Outputs for alarm devices can be collectively disabled and re-enabled via this menu (B9).
  • Page 21: Disable / Re-Enable Outputs For Routing Equipment (B10)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual 5.10 Disable / re-enable outputs for routing equipment (B10) Not available for users with access level / type "Information only". Disabled outputs for routing equipment are listed in menu H4/U1.
  • Page 22: Disable / Re-Enable Alert Annunciation Function (B11)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual 5.11 Disable / re-enable alert annunciation function (B11) Not available for users with access level / type "Information only". Normal operation: For alarm points / zones programmed for Alert Annunciation (via EBLWin) is normally the AA function enabled via a time channel, e.g.
  • Page 23: Set Calendar And Clock (H3)

    When required, the clock can be corrected, so that the "time stamps" for fire alarms, faults, etc. will be correct. NOTE! The RTC component has no built-in battery, i.e. if EBL128 has been powerless (no mains and no battery backup) and after software download, the date, day of the week and the time have to be set when EBL128 is powered-up again.
  • Page 24: Present System Status (H4)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Present system status (H4) Disablement (U1) A list of all disablements (done via menu H2/Bx). Also alarm points that have been automatically disabled ("encupsulated") in conjunction with fire alarm reset.
  • Page 25: Disablement By Time Channel (U2)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Disablement by time channel (U2) Only disablements by time channel will be displayed in menu U2. Other disablements will be displayed in menu U1. If the list is empty, "...
  • Page 26: Sensor Values (U3)

    Press "Return" (P9) two times to menu U3.  Scroll to another menu or press "Return" to menu H4. Scroll to another menu or leave the menu system by pressing "Return". The information is described in EBL128 Operating Instructions MEW01623.
  • Page 27: Sensors Activating Service Signal (U4)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Sensors activating SERVICE signal (U4) Service signal is indicated by LED "Service" (L12). The week average sensor value is over the service level respectively for one or more detectors / sensors.
  • Page 28: Technical Warning (U5)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Technical warning (U5) One or more Technical warnings in the system are indicated in the display with Menu U5 is a list of the Technical warnings in the system.
  • Page 29: Event Log (U6)

    MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Event log (U6) Presentation of the events in EBL128 is divided into three event lists, Alarm, Interlocking and General respectively. The event lists can also be read via EBLWin and the Web-server II.
  • Page 30: Version And Alarm Counter (U7)

    EBL128 version 2.0.x, Daily user's manual Version and alarm counter (U7) Version: The EBL128 software / firmware version. Alarm counter The alarm counter is increased with "1" every time the c.i.e. enters the real "fire alarm condition" (Fire alarm indication in the display, LEDs "Fire"...
  • Page 31: Fault Acknowledge (H6)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual FAULT Acknowledge (H6) Users with access level / type "Information only" can only see the fault messages, not acknowledge the faults. LED "General fault" (L7) is indicating that not all faults are acknowledged and/or corrected.
  • Page 32: Perform Zone Test (H7)

    There will be an automatic ending of the test mode one hour after the latest tested alarm point / zone. NOTE! If the door in EBL128 is left open, the output(s) for routing equipment (fire brigade tx) might be disabled (if set so in EBLWin).
  • Page 33: Interlocking Outputs And Inputs (H9)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Interlocking outputs and inputs (H9) Each interlocking combination (Area - Point) normally contains one interlocking output and one interlocking input. 10.1 Activated interlocking outputs / inputs (C1) If there are no interlocking outputs / inputs activated, --- List is empty --- will be shown.
  • Page 34: Activate Interlocking Output (C2)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual 10.2 Activate interlocking output (C2) Not available for users with access level / type "Information only". The output in each interlocking combination (Area - Point) can be manually activated via this menu (C2).
  • Page 35: Reset Interlocking Output (C3)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual 10.3 Reset interlocking output (C3) Not available for users with access level / type "Information only". Interlocking output activated via its control expression and with latching output selected (in EBLWin): The output has to be reset via this menu (C3).
  • Page 36: Disable Interlocking Output (C4)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual 10.4 Disable interlocking output (C4) Not available for users with access level / type "Information only". Up to 100 Interlocking outputs (Type = Interlocking) can be individually disabled via this menu (C4) but not via menu H2.
  • Page 37: Re-Enable Interlocking Output (C5)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual 10.5 Re-enable interlocking output (C5) Not available for users with access level / type "Information only". Disabled interlocking outputs are listed in menu H4/U1. Individually disabled interlocking outputs (Type = Interlocking) have to be re-enabled via this menu (C5).
  • Page 38: Change Password (H10)

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Change password (H10) You can change the Password for the User name that was used for log on to the control unit. An incorrect password will result in no change.
  • Page 39: Revision History

    Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual Revision history...
  • Page 40 Panasonic Eco Solutions Nordic AB MEW01624 Rev: - EBL128 version 2.0.x, Daily user's manual...
  • Page 41 This page has deliberately been left blank.
  • Page 42 Panasonic Eco Solutions Nordic AB Jungmansgatan 12, SE-211 19 Malmö, Sweden Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 info.pesn@eu. panasonic.com • http://pesn.panasonic.se...