Sensitive fault detection mode (H5/A2)

To increase the possibilities to detect faults during the commissioning,
it is possible to use the "Sensitive fault detection mode. (The time
delay for each fault will be reduced).
NOTE! Don't forget to turn off this mode after the commissioning.
Text in display
Sensitive fault detection mode
Sensitive fault detection mode: 0
(0 = off, 1 = on)
Sensitive fault detection mode
Operating Instructions Fire alarm system EBL512 V2.3.x
ACCEPT? A2
ACCEPT? A2
106
Comments
According to chapter
"Access code for service
(H5)", see page 104.
Press "A" or "1" and "A"
to accept. ON is indicated
by LED "Fault tx
activated" (L11) and the
"Fault" output for routing
equipment. This mode is
ON until turned OFF in
this menu (A2).
Scroll or press "Return" to
H5. Scroll or press
"Return" to log off.