After this phase, a triple beep will be heard, the compressor switches off, the display will show a
blinking „o" and the LED „START" will lighten up.
It's time now to discharge the contaminants (oil and particles) from the distillation chamber, but first it´s
necessary to add pressure to chamber, so that oil and particles can flow out through the drain valve.
On the back side of the unit, just above the power cable, you can find the drain valve.
When this valve is opened, vapour of SOLSTICE
®
PF-C will flow into the distillation chamber.
Please place the short rubber hose provided and a suitable fluid container (bottle, pail,...) to collect the
contaminant, open the drain valve of the distillation chamber and then open the valve on the back side
of the unit.
The pressure of the vapour of SOLSTICE
®
PF-C will push oil, particles and dirt out from the distillation
chamber. When the flow will stop, close both valves.
To continue with the distillation, press „START.
®
If the solvent cylinder with dirty SOLSTICE
PF-C (to be distilled) is empty, the LED „CLEAN" will turn
on and the display will show „o" at the same time.
From this moment, the distillation will take approximately another 7 min, after which you will hear
three beeps, the display will show „o" and the LED „START "will blink.
Finally, discharge the contaminants (oil and particles) from the distillation chamber as described
above, then press „START", the LED „CLEAN" will blink and the units will evacuate the vapour of
®
SOLSTICE
PF-C from the cylinder.
When the pressure on the low-pressure manometer will go under 0 bar, it´s necessary to stop this
programme by pressing „END".
The final evacuation of the vapours takes max. 15 minutes, then the compressor will switch off
automatically. No need to press „END" again.
Warning!
During the distillation process, it´s necessary to check the filter in the sight glass „OUT", because if
that filter will accumulate a lot of dirt, the flow may be limited, and the unit will respond as if the
cylinder with dirty SOLSTICE
®
PF-C is empty.
If this happens, press „END" (the LED „START" will blink), close the hose valve (red) at the sight glass
and clean the filter in the sight glass (see paragraph 7.4) and the filter P48 if you are using it.
Once the filters have been cleaned and placed in the original position, open the liquid valve (red) and
continue the distillation by pressing „START".
PLEASE NOTE
In case you are using the filter P48 too, you can realize that the flow has been stopped only by
weighing the cylinder with the dirty solvent.
Should you have remaining solvent to distillate, stop the flow as described above (press "END" and
close hose valve at the filter) and clean the P48 filter, then continue the process by pressing "START".
- 15 -