Honeywell EkoFlush-K572 User's Operating Manual
Honeywell EkoFlush-K572 User's Operating Manual

Honeywell EkoFlush-K572 User's Operating Manual

Wheeled circuit flushing unit

Advertisement

Wheeled Circuit Flushing Unit
EkoFlush-K572
USER OPERATING MANUAL
- 1 -

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell EkoFlush-K572

  • Page 1 Wheeled Circuit Flushing Unit EkoFlush-K572 USER OPERATING MANUAL - 1 -...
  • Page 2: Table Of Contents

    • bar or less should be shown on the low-pressure manometer). The EkoFlush-K572 unit can only be transported by transportation means if its solvent cylinder is • disconnected and transported separately. The main unit can be transported on wheels (properly protected against moving), or laid down on its rear side leaning on its handle and wheels.
  • Page 3: Unit Description

    3. Unit Description The EkoFlush-K572 is a mobile flushing unit with wheels and rugged metal structure. The solvent cylinder required to operate the machine must have a two-way valve and must be filled ® only with the flushing agent SOLSTICE PF-C by HONEYWELL, pressurized with nitrogen at 8 bar.
  • Page 4: Accessories

    Main dimensions (WxDxH) 570x605x950 (mm) • ® Flushing agent for systems cleaning SOLSTICE PF-C • !! WARNING !! The Flushing Unit EkoFlush-K572 is designed to operate exclusively with ® the SOLSTICE PF-C flushing solvent produced by HONEYWELL. - 4 -...
  • Page 5: Main Principles And Interconnections

    6. Main principles and interconnections The circuit to flush must be tight, free from leaks and from internal blocks. IMPORTANT! Please check the absence of internal blocks by flowing some nitrogen or air through the circuit, before starting the flushing operations. The pressure of the solvent and the EkoFlush unit may not be sufficient to remove the blocks and the flushing operation will not be completed, resulting in loss of solvent.
  • Page 6 6.11 Check the oil level in the compressor sight-glass and refill if necessary. The level of the oil must be between those two lines, indicated in the picture below. Picture 2 - Sight-glass for compressor oil WARNING! Any claim for malfunctioning caused by lack of oil won’t be accepted!! 6.12 Connect the front panel of the EkoFlush K572 to the circuit to flush, as follows: inlet into the flushed circuit to “IN”...
  • Page 7: Flushing Procedure

    7. Device flushing procedure Blue Main Switch Pos. 31 Low Pressure Picture 3 - Cylinder of Solstice® (from circuit) PF-C Pos.16 Manometers High Pressure OUTLET HOSE (from cylinder) with Valve Pos.13 Sight Glasses Outlet Inlet Pos.6 Pos.7 Picture 4 - K572 Control panel INLET HOSE with Valve High Pressure...
  • Page 8 At the beginning of the flushing process, the unit automatically evacuates the circuit to clean ® from the air, then automatically fills it with the solvent SOLSTICE PF-C. PLEASE NOTE For circuits with more sections, the following steps are recommended: As soon as the sight glass (Picture 4 - Pos.6) is filled with the liquid, close the valve on the hose connected to the outlet marked "OUT"...
  • Page 9 Picture 6 - Solvent front sight-glass distmantled After dismantling the upper part (No. 2, 3, 4), withdraw the blocking spring (No.4) and dismantle all single parts (No.2, No.3 and No.4) and clean them, together with the interior of the sight glass (No. 1). CLEANING THE P48 FILTER The cleaning of the P48 Filter is extremely simple: - Open the external cartridge by unscrewing it...
  • Page 10: Controlling

    8. Unit controlling – work flow G = green Y = yellow PB = button LED = diode-signal light Picture 7 - K572 Switchboard DISPLAY or LEDS 8.1. Turn on the main switch. The display shows the number of remaining flushing procedures three times.
  • Page 11 Remark : If the electric power is interrupted when the procedure at point 8.2 is in process (from the pressing of “START” until the first acoustic signal), LED 1 blinks after electric power has been renewed. You need to press PB 1 – START again to continue the program from the point it had stopped (the last active process step is repeated from its beginning).
  • Page 12 Open Picture 8 - Discharge of oil and dirt IMPORTANT NOTE 1) The low-pressure manometer (Picture , Pos. 16) – shows the pressure in the circuit being flushed. It does not show any overpressure in the distillation chamber. 2) Oil and sludge can also be discharged from the distillation chamber after the flushed circuit is disconnected.
  • Page 13: Completing Flushing

    7) The maximum capacity of the distillation chamber for oil and residues is about 1 liter. If during the flushing this capacity is filled with contaminants, LED7 (Distillation Chamber Full) will not switch off and the process can “freeze”. It is necessary to discharge the distillation chamber, but first it´s necessary to add pressure to chamber, so that oil and particles can flow out through the drain valve.
  • Page 14: Exchange Of Solstice Pf-C Solvent

    Exchange of SOLSTICE PF-C solvent ® Honeywell recommends to replace the flushing solvent SOLSTICE PF-C after 20 flushing operations. The real efficiency in the purification of the flushing solvent depends on the type and level of the fouling of the cleaned equipment.
  • Page 15 After this phase, a triple beep will be heard, the compressor switches off, the display will show a blinking „o“ and the LED „START“ will lighten up. It’s time now to discharge the contaminants (oil and particles) from the distillation chamber, but first it´s necessary to add pressure to chamber, so that oil and particles can flow out through the drain valve.
  • Page 16: Oil Change, Adding Oil

    12.1 Oil change New complete filling is 0,4 liters of recomended oil. During filling, it is necessary to place a sufficient volume of oil in a suitable container under the oil inlet (pos. 33), so that the hose fitted to the valve reaches the bottom of the vessel.
  • Page 17: Waste Disposal

    ® Waste Disposal (SOLSTICE PF-C flushing liquid and waste product) A cylinder of SOLSTICE PF-C can be used to flush efficiently a maximum of 20 circuits, after which you can still use the solvent for a final Open-flush operation (vented to air). Please return the empty cylinder of SOLSTICE PF-C to your local supplier.
  • Page 18: Failures, Possible Causes, Troubleshooting Guide

    Failures, Possible Causes, Troubleshooting Guide Problems / Defects Possible Cause Suggested Solution After switching on, the Energy supply defect. Check power cable, plug and signal light does not turn distribution circuit breaker. The unit works but under- a) Leakage in connection or a) Check all connections –...
  • Page 19 Problems / Defects Possible Cause Suggested Solution The pressure on LP The circuit is clogged. Close the valves on the hoses at flushing unit. manometer is lower than (on the hoses interconnecting flushing unit and minus 0.5 bar, but in the circuit to flush –...
  • Page 20: Ce Conformity Declaration, Certificate Electro-Technical Testing Institute

    CE Conformity Declaration - 20 -...
  • Page 21: Safety Guidelines

    19.5° C at 1 atm. Pressure (101,325 kPa) Colorless, vaporous fluid with slightly sweetish odor, non-flammable Producer: Honeywell Fluorine Products Europe BV Laarderhoogtweg 18, 1101 EA Amsterdam, The Netherlands MANIPULATION: The flushing solvent has been designed for the cleaning of cooling and refrigerating circuits during maintenance and repair operations.
  • Page 22: K572 Optional Accessories To Order

    ITEM DESCRIPTION PHOTO connecting pipes diameter 8 - 18mm Pipe with flange connection (if used with EkoFlush-K572 it is necessary to Order number: 352 00560 use reduction for hose connection) connecting pipes diameter 8 - 18mm Pipe connection 8-18 mm...
  • Page 23 Manufacturer: For Honeywell: Ekotez Ltd. Koněvova 47 CZ-13000 Prague 3 Czech Republic Franchise Dealer – Reseller: Remark: - 23 -...

Table of Contents