Neutral CT Adapter 150A-5000A

This is a miniature Rogowski coil. It mounts between the incoming Neutral CT and the breaker trip unit. It
converts the signal from an iron Core Neutral sensor to a Rogowski voltage output which is wired to the
Breaker's Trip Unit Neutral input connections.
The Neutral CT Adapter supports iron core Neutral sensors compatible with MicroVersa Trip, MVT RMS-9,
Power Plus, Pro Trip and EntelliGuard TU rated from 150 to 5000Amps as used in GE switchboards and
switchgear. It is available in five variations (shown in below Table).
Catalog Number
RNCTA1200 (R)
RNCTA2000 (R)
RNCTA3000 (R)
RNCTA4000 (R)
RNCTA5000 (R)
AKD-10—Rogowski Assemblies, Mechanical Views
Figure 25 shows a typical Rogowski assembly.
Figure 25. Neutral Bus Rogowski ASM 10108266
EntelliGuard R Circuit Breaker Retrofill AKD-10 Installation Manual
46
Supported Neutral CT ratings (A)
600, 1200
150, 200, 400, 800, 1000, 1600, 2000
3000
2500, 3200, 4000
5000
DEH41550 R06