Quick Links

Introduction
Key Interlock Kit:
The breaker key lock is an optional accessory,
which will keep the breaker in trip free state while
locked. Maximum 4 keys of Ronis/Profalux or Kirk
type can be used. All EntelliGuard Devices can be
equipped with one of the three locks, that when
fitted as indicated allow the use of one to four key
locks that lock the device in its open position.
Figure 1. (A) Front Cover
DEH-41407 Installation Instructions
EntelliGuard
Accessories
Key Interlock Kit Breaker Mounted
WARNING: Before installing any accessories, turn
the breaker OFF, disconnect it from all voltage
sources, and discharge the closing spings.
AVERTISSEMENT: Avant d'installer tout accessoire,
mettre le disjoncteur en position OFF, le
déconnecter de toute tension d'alimentation , et
décharger les resorts d'armement
Devices are found in two Variants:
1. Factory mounted mechanism:
The breaker/device is supplied off works with all
cams and screws allowing the user to mount a
separately acquired GE type lock kit.
2. Field mountable device:
A kit is supplied allowing the field mounting of the
locking mechanism and allowing the use of a lock
of the correct type purchased elsewhere
Catalog Number:
Catalog No
Description
GBKRKR
Kirk Key Interlock kit
GBRONR
Ronis Interlock kit
GBPROR
Profalux Interlock kit
Installation of kit
Use the following procedure to install the Key
Interlock Key accessory into the circuit breaker.
1. Turn the breaker off and discharge the closing
springs by depressing the OFF and ON buttons in
the sequence OFF-ON-OFF. Verify that the
breaker OFF-ON indicator shows OFF and that the
charge indicator shows DISCHARGE. If installing
in a draw-out type breaker remove breaker from
adaptor (cassette) before continuing.
1
®
G Circuit Breaker

Advertisement

loading

Summary of Contents for GE EntelliGuard GBKRKR

  • Page 1 1. Factory mounted mechanism: The breaker/device is supplied off works with all cams and screws allowing the user to mount a separately acquired GE type lock kit. 2. Field mountable device: A kit is supplied allowing the field mounting of the...
  • Page 2 2. Loosen the 6 screws on front cover (fascia) 6. Using the nut supplied with each lock fix the using a posidrive screw driver as shown in Fig 1.B activating CAM. Ensure that the CAM is positioned Rotate the charging handle down and slide the as indicated in fig.
  • Page 3 8. Uninstall the Motor operator (Optional if present), Grounding nut & Nylock nut as shown. Fig 4. Grounding nut Nylock nut Figure 4. 9. Install adaptor nut and torque to 6Nm. Mount the support bracket on grounding stud and adaptor nut at other end. Secure support bracket with hardware removed/provided.
  • Page 4 These instructions do not purport to cover all details or variations in equipment nor, to provide contingency to be met in connection with installation, operation, or maintenance. Should further information be desired, or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to GE. 41 Woodford Ave, Plainville, CT 06062 www.geelectrical.com...

This manual is also suitable for: