Honeywell HPM Service page 54

High-performance process manager
Table of Contents

Advertisement

2 Equipment Description
2.7 Service failed EHPM cards flashed with Experion-integrated firmware
8.
9.
10.
11.
12.
13.
14.
54
Power-off the new EHPM Comm/Ctrl card in the FILE_2 or RIGHT card file position
by temporarily pulling out the High-Performance I/O Link card about 2 inches (but
leave the I/O Link card in the card file chassis) from the HPM card file chassis.
Remove the newly flashed EHPM card, and place it back into its static-free bag. It is
ready now for use in another EHPM chassis.
To recover the existing backup EHPM, take the existing EHPM card from the static-
free surface, and insert it into the empty slot in the FILE_2 or RIGHT card file
position.
Reconnect the 3rd port redundancy cable (orange port) to the FTE Interface card.
Re-insert the High-Performance I/O Link card to power-on the EHPM Comm/Ctrl
card.
The existing, original Experion-integrated replacement EHPM Comm/Ctrl card in the
FILE_2 or RIGHT card file position will go to the ALIVE state and is ready to be
loaded.
Load the EHPM Comm/Ctrl card from the ALIVE state to the BACKUP state.
HPM High-Performance Process Manager Service