3 UCN Status Displays
3.4 Display Operation
UCN CABLE STATUS targets
The following table defines the functions of the UCN CABLE STATUS targets.
Target
TEST/SEL CABLE A
TEST/SEL CABLE B
ENABLE SWAP
DISABLE SWAP
ALL NODES
CANCEL
ENTER
202

Table 29 UCN CABLE STATUS Target Selected

Initiates a Backup Cable Test sequence for UCN cable A. If
no faults are detected, UCN cable A is activated for all UCN
devices. The command is executed by selecting the ENTER
target.
Initiates a Backup Cable Test sequence for UCN cable B. If
no faults are detected, UCN cable B is activated for all UCN
devices. The command is executed by selecting the ENTER
target.
Enables periodic swapping of the UCN cables. The
command is executed by selecting the ENTER target.
Disables periodic swapping of the UCN cables. The
command is executed by selecting the ENTER target.
Enables all UCN nodes to be affected by the cable function.
Clears the BACKUP CABLE TST, TEST/SEL CABLE A,
TEST/SEL CABLE B, ENABLE SWAP, DISABLE SWAP,
UCN COMM STATUS, ALL NODES, and ENTER command
targets from the display.
The ENTER target must be selected for the chosen UCN
CABLE STATUS function to be executed.
HPM High-Performance Process Manager Service
Honeywell
Function
R688