3.3.6 Ullage readout

When an ullage reading is required, the two items shown below
must be changed.
The ullage value is also transmitted to the host via the 2-wire
Honeywell Enraf field bus (or optional RS-channel).
The ullage, or outage, measurement is referred to a 'zero' point at
the tank top (upper reference point).
The level, or innage, measurement is referred to a 'zero' point at
the tank bottom (datum plate).
Refer to figure
Note:
The high and low level alarms are "innage" alarms.
Hence a high alarm condition occurs when there is
a low ullage value and visa verse.
Item
Name
W2=
Protection level 2
UR= Upper reference
DE= Level type
EX
Exit
Instruction manual 854 ATG
Description
Enter protection level 2 (default password: ENRAF2)
Format according to item LD.
The distance UR represents the distance from the 'innage' zero point
(datum plate) to the upper reference point at a dip hatch (or other point
at the tank top).
One character; either C, I or U.
C :
for hydrostatic deformation compensated innage measurement
I :
for innage measurement (default)
U :
for ullage measurement
Exit protection level.
Commissioning
Figure 3.8
Upper reference value
Page 21