Honeywell CIU 888 Troubleshooting And Maintenance Manual page 11

Hide thumbs Also See for CIU 888:
Table of Contents

Advertisement

No.
Item
11
Option slot status
12
Security option
13
Software option
14
Hardware option
Part No.: 4417594_Rev11
Diagnostics
Description
Indicates the overall health of the option slots and the gauges connected to
it. The first four icons represent field cards and the last two icons can
represent a field card, a host port card or a CIU emulation card.
Running
The health state of the option slot and the state of all connected
gauges is optimal.
Service
The state of one or more of the connected gauges is set to service
and the option slot and all connected gauges are not in error state.
This state is also used when option slot is present but not
configured.
Error
The health state of the option slot or one of the connected gauges is
set to error.
Available
The option slot is empty.
The last two option slots can have the following states:
Running
An option card is present and configured.
Service
An option card is present but not configured.
Available
The option slot is empty.
Note:
For passive CIU, Option Slot status for configured field ports is
always indicated as 'Running'.
Not supported currently.
Gives access to information about the software version. Refer to
section 1.2.3 for more information.
Not supported currently.