Test configuration
Checking the system for
leaks
HON 5020 gas pressure regulator with HON 630 pilot
The test setup is as follows (schematic diagram, using the two-stage HON 630 pilot with a
diaphragm assembly as a reference):
The numbers have the following meaning:
No.
Meaning
1
Inlet chamber
2
Outlet chamber
Inlet stop valve armature
3
Gas pressure regulator
4
Outlet stop valve armature
5
Proceed as follows:
Step
Description
1
Slowly close the outlet stop valve armature.
2
Apply the test medium to all detachable pipe joints.
3
Observe the test medium on all detachable pipe joints for several minutes.
If ...
no foam or bubbles are formed
foam or bubbles are formed
Step
Description
4
Slowly close the inlet stop valve armature.
5
Depressurize the inlet chamber and the outlet chamber.
6
Seal the leaking pipe joints.
7
Repeat the leak test starting with step 1.
Transport and installation
then ...
the system is leak-proof.
the system may be put into operation.
the affected pipe joint is leaking.
the system may not be put into operation.
Proceed with step 4.
38