GE EPM6000 Instruction Manual page 114

Multi-function power meter
Hide thumbs Also See for EPM6000:

Advertisement

MODBUS REGISTER MAP
Hex
Decimal
7535 - 7535 30006 - 30006 Power & Energy
7536 - 7536 30007 - 30007 Operating Mode
7537 - 753D 30008 - 30014 Reserved
753E - 753E 30015 - 30015 User Settings Flags
753F - 753F 30016 - 30016 Full Scale Current (for
7540 - 7547 30017 - 30024 Meter Designation
7548 - 7548 30025 - 30025 COM1 setup
7549 - 7549 30026 - 30026 COM2 setup
754A - 754A 30027 - 30027 COM2 address
754B - 754B 30028 - 30028 Limit #1 Identifier
754C - 754C 30029 - 30029 Limit #1 Out High
754D - 754D 30030 - 30030 Limit #1 In High
754E - 754E 30031 - 30031 Limit #1 Out Low
B–10
Table Appendix B –1: Modbus Register Map (Sheet 6 of 9)
1
Format
Description
UINT16 bit-mapped
Format
UINT16 bit-mapped
Screen Enables
UINT16 bit-mapped
UINT16 0 to 9999
load % bargraph)
ASCII
UINT16 bit-mapped
UINT16 bit-mapped
UINT16 1 to 247
UINT16 0 to 65535
SINT16 -200.0 to +200.0
Setpoint
SINT16 -200.0 to +200.0
Threshold
SINT16 -200.0 to +200.0
Setpoint
APPENDIX B: MODBUS MAPPING FOR EPM6000
Units or
6
Range
Resolution
pppp--nn -eee-
ddd
00000000
eeeeeeee
---g--nn srp--wf- g = enable alternate full
none
16 char
none
----dddd -
0100110
----dddd -ppp-
bbb
none
0.1% of full scale Setpoint for the "above"
0.1% of full scale Threshold at which "above"
0.1% of full scale Setpoint for the "below"
EPM6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE
Comments
pppp = power scale (0-unit,
1
3-kilo, 6-mega, 8-auto)
nn = number of energy
digits (5-8 --> 0-3)
eee = energy scale (0-unit,
3-kilo, 6-mega)
ddd = energy digits after
decimal point (0-6)
See note 10.
eeeeeeee = op mode screen
1
rows on(1) or off(0), rows top
to bottom are bits low order
to high order
7
1
scale bargraph current
(1=on, 0=off)
nn = number of phases for
voltage & current screens
(3=ABC, 2=AB, 1=A, 0=ABC)
s = scroll (1=on, 0=off)
r = password for reset in use
(1=on, 0=off)
p = password for
configuration in use (1=on,
0=off)
w = pwr dir (0-view as load,
1-view as generator)
f = flip power factor sign
(1=yes, 0=no)
If non-zero and user
1
settings bit g is set, this
value replaces CT
numerator in the full scale
current calculation.
8
dddd = reply delay (* 50
1
msec)
ppp = protocol (1-Modbus
RTU, 2-Modbus ASCII, 3-
1
DNP)
bbb = baud rate (1-9600, 2-
19200, 4-38400, 6-57600)
1
use Modbus address as the
1
identifier (See notes 7, 11,
1
limit (LM1), see notes 11-12.
1
limit clears; normally less
than or equal to the "above"
setpoint; see notes 11-12.
1
limit (LM2), see notes 11-12.
#
R
e
g

Hide quick links:

Advertisement

loading