Download Print this page
GE Multilin EPM 2200 Instruction Manual
GE Multilin EPM 2200 Instruction Manual

GE Multilin EPM 2200 Instruction Manual

Multi-function power meter
Hide thumbs Also See for Multilin EPM 2200:

Advertisement

Quick Links

Digital Energy
Multilin
Instruction Manual
Software Revision: 1.01
Manual P/N: 1601-9111-A2
Manual Order Code: GEK-113575A
Copyright © 2011 GE Multilin
GE Multilin
215 Anderson Avenue, Markham, Ontario
Canada L6E 1B3
Tel: (905) 294-6222 Fax: (905) 201-2098
Internet:
http://www.GEmultilin.com
*1601-9111-A2*
EPM 2200 Multi-function Power
Chapter 1:
Metering System
I I SO9001:2000
GE Multilin's Quality
Management System is
registered to ISO9001:2000
QMI # 005094

Advertisement

loading

Summary of Contents for GE Multilin EPM 2200

  • Page 1 Metering System Chapter 1: Instruction Manual Software Revision: 1.01 Manual P/N: 1601-9111-A2 Manual Order Code: GEK-113575A Copyright © 2011 GE Multilin GE Multilin I I SO9001:2000 215 Anderson Avenue, Markham, Ontario Canada L6E 1B3 GE Multilin's Quality Tel: (905) 294-6222 Fax: (905) 201-2098...
  • Page 3: Table Of Contents

    Table of Contents THREE-PHASE SYSTEM CONFIGURATIONS ................1-1 1: THREE-PHASE ......................1-1 POWER ONNECTION ......................1-3 MEASUREMENT ELTA ONNECTION ’ ......... 1-5 LONDELL HEOREM AND HREE HASE EASUREMENT POWER, ENERGY AND DEMAND ....................1-8 ..........................1-10 EMAND REACTIVE ENERGY AND POWER FACTOR ................1-12 ................
  • Page 4 (8) C ) ............ 4-16 URRENT EASUREMENT HREE HASE (9) C ) ............4-17 URRENT EASUREMENT HASE (10) C ) ..........4-18 URRENT EASUREMENT INGLE HASE EPM2200 COMMUNICATION ...................... 5-1 5: COMMUNICATION RS-485 / KYZ O COM 2 (485P O ) ............
  • Page 5: Wye Connection

    Digital Energy Multilin EPM 2200 Multi-function Power Metering System Chapter 1: Three-Phase Power Measurement Three-Phase Power Measurement This introduction to three-phase power and power measurement is intended to provide only a brief overview of the subject. The professional meter engineer or meter technician should refer to more advanced documents such as the EEI Handbook for Electricity Metering and the application standards for more in-depth and technical coverage of the subject.
  • Page 6 CHAPTER 1: THREE-PHASE POWER MEASUREMENT FIGURE 1–1: Three-phase Wye winding The three voltages are separated by 120 electrically. Under balanced load conditions with unity power factor the currents are also separated by 120 . However, unbalanced loads and other conditions can cause the currents to depart from the ideal 120 separation.
  • Page 7: Delta Connection

    CHAPTER 1: THREE-PHASE POWER MEASUREMENT The following table indicates the common voltages used in the United States for wye connected systems. Table 1–1: Common Phase Voltages on Wye Services Phase-to-Ground Voltage Phase-to-Phase Voltage 120 volts 208 volts 277 volts 480 volts 2400 volts 4160 volts 7200 volts...
  • Page 8 CHAPTER 1: THREE-PHASE POWER MEASUREMENT FIGURE 1–3: Three-phase Delta Winding Relationship In this example of a delta service, three wires will transmit the power to the load. In a true delta service, the phase-to-ground voltage will usually not be balanced because the ground is not at the center of the delta.
  • Page 9: Blondell S Theorem And Three Phase Measurement

    CHAPTER 1: THREE-PHASE POWER MEASUREMENT 120 V 120 V FIGURE 1–5: Three-Phase, Four-Wire Delta Phasors 1.1.3 Blondell’s Theorem and Three Phase Measurement In 1893 an engineer and mathematician named Andre E. Blondell set forth the first scientific basis for poly phase metering. His theorem states: •...
  • Page 10 CHAPTER 1: THREE-PHASE POWER MEASUREMENT In modern digital meters, Blondell's Theorem is still applied to obtain proper metering. difference in modern meters is that the digital meter measures each phase voltage and current and calculates the single-phase power for each phase. The meter then sums the three phase powers to a single three-phase reading.
  • Page 11 CHAPTER 1: THREE-PHASE POWER MEASUREMENT power flow in three wires. This will require three voltage coils and three current coils (a three element meter). Similar figures and conclusions could be reached for other circuit configurations involving delta-connected loads. EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE 1–7...
  • Page 12: Power, Energy And Demand

    CHAPTER 1: THREE-PHASE POWER MEASUREMENT Power, Energy and Demand It is quite common to exchange power, energy and demand without differentiating between the three. Because this practice can lead to confusion, the differences between these three measurements will be discussed. Power is an instantaneous reading.
  • Page 13 CHAPTER 1: THREE-PHASE POWER MEASUREMENT The data from Figure 1-7 is reproduced in the table below to illustrate the calculation of energy. Since the time increment of the measurement is one minute and since we specified that the load is constant over that minute, we can convert the power reading to an equivalent consumed energy reading by multiplying the power reading times 1/60 (converting the time base from minutes to hours).
  • Page 14: Demand

    CHAPTER 1: THREE-PHASE POWER MEASUREMENT Figure 1.8 shows another example of energy and demand. In this case, each bar represents the energy consumed in a 15-minute interval. The energy use in each interval typically falls between 50 and 70 kWh. However, during two intervals the energy rises sharply and peaks at 100 kWh in interval number 7.
  • Page 15 CHAPTER 1: THREE-PHASE POWER MEASUREMENT Intervals (15 mins.) FIGURE 1–8: Energy Use and Demand Intervals As seen in this example, it is important to recognize the relationships between power, energy and demand in order to effectively control loads or to correctly monitor use. EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM –...
  • Page 16: Reactive Energy And Power Factor

    CHAPTER 1: THREE-PHASE POWER MEASUREMENT Reactive Energy and Power Factor 1.3.1 Real, Reactive, and Apparent Power The real power and energy measurements discussed in the previous section relate to the quantities that are most used in electrical systems. But it is often not sufficient to only measure real power and energy.
  • Page 17: Power Factor

    CHAPTER 1: THREE-PHASE POWER MEASUREMENT So keeping the VAR content low allows a line to carry its full capacity of watts. In order to encourage customers to keep VAR requirements low, most utilities impose a penalty if the VAR content of the load rises above a specified value. 1.3.2 Power Factor A common method of measuring reactive power requirements is power factor.
  • Page 18: Harmonic Distortion

    CHAPTER 1: THREE-PHASE POWER MEASUREMENT Harmonic Distortion Harmonic distortion is primarily the result of high concentrations of non-linear loads. Devices such as computer power supplies, variable speed drives and fluorescent light ballasts make current demands that do not match the sinusoidal waveform of AC electricity.
  • Page 19: Inductive And Capacitive Impedance

    CHAPTER 1: THREE-PHASE POWER MEASUREMENT collection of higher frequency waveforms. These higher frequency waveforms are referred to as harmonics. Figure 1.12 shows the content of the harmonic frequencies that make up the distortion portion of the waveform in Figure 1-11. -100 -150 -200...
  • Page 20: Waveform Capture

    CHAPTER 1: THREE-PHASE POWER MEASUREMENT accuracy; at frequencies above about 1200 Hz they pass almost no information. So when instrument transformers are used, they effectively filter out higher frequency harmonic distortion making it impossible to see. However, when monitors can be connected directly to the measured circuit (such as direct connection to 480 volt bus) the user may often see higher order harmonic distortion.
  • Page 21: Power Quality

    CHAPTER 1: THREE-PHASE POWER MEASUREMENT Power Quality Power quality can mean several different things. The terms ‘power quality’ and ‘power quality problem’ have been applied to all types of conditions. A simple definition of ‘power quality problem’ is any voltage, current or frequency deviation that results in mis-operation or failure of customer equipment or systems.
  • Page 22 CHAPTER 1: THREE-PHASE POWER MEASUREMENT 1–18 EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE...
  • Page 23: Specifications

    Digital Energy Multilin EPM 2200 Multi-function Power Metering System Chapter 2: Overview and Specifications Overview and Specifications Hardware Overview The EPM2200 monitor is a 0.5% class electrical panel meter. Using bright and large .56” LED displays, it is designed to be used in electrical panels and swtichgear. The meter has a unique anti-dither algorithm to improve reading stability.
  • Page 24: Order Codes

    CHAPTER 2: OVERVIEW AND SPECIFICATIONS The CT passes directly through the meter without any physical termination on the meter. This insures that the meter cannot be a point of failure on the CT circuit. This is preferable for utility users when sharing relay class CTs. No Burden is added to the secondary CT circuit.
  • Page 25: Utility Peak Demand

    CHAPTER 2: OVERVIEW AND SPECIFICATIONS Table 2–2: EPM 2200 Measured Values Measured Values Real Time Average Maximum Minimum Negative watt-hours Net watt-hours Positive VAR-hours Negative VAR-hours Net VAR-hours VA-hours Frequency Voltage angles Current angles % of load bar 2.1.4 Utility Peak Demand The EPM 2200 provides user-configured Block (fixed) window, or Rolling window demand.
  • Page 26: Specifications

    CHAPTER 2: OVERVIEW AND SPECIFICATIONS Specifications POWER SUPPLY Range:..............Universal, (90 to 265) VAC @50/60Hz Power consumption:........5 VA VOLTAGE INPUTS (MEASUREMENT CATEGORY III) Range:..............Universal, Auto-ranging up to 416 V AC L-N, 721 V AC L-L Supported hookups:........3-element Wye, 2.5-element Wye, 2-element Delta, 4-wire Delta Input impedance: ...........1 MOhm/phase Burden: ..............0.0144 VA/phase at 120 Volts...
  • Page 27 CHAPTER 2: OVERVIEW AND SPECIFICATIONS For 2.5 element programmed units, degrade accuracy by an additional 0.5% of reading. For unbalanced voltage inputs where at least one crosses the 150V auto-scale threshold (for example, 120V/120V/208V system), degrade accuracy by additional 0.4%. EPM 2200 accuracy meets the IEC62053-22 Accuracy Standards for 0.5% Class Meters.
  • Page 28 CHAPTER 2: OVERVIEW AND SPECIFICATIONS Infrared LED: Peak Spectral Wavelength: ......940nm Reset State: ............Off FIGURE 2–1: Internal Schematic (De-energized State) FIGURE 2–2: Output Timing 2–6 EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE...
  • Page 29 CHAPTER 2: OVERVIEW AND SPECIFICATIONS COMMUNICATIONS PORTS Protocols: ............Modbus RTU, Modbus ASCII Baud rate: ............9600 to 57600 bps Port address: ............001 to 247 Data format: .............8 bits, no parity MECHANICAL PARAMETERS Dimensions: ............4.25" × 4.82" × 4.85" (L × W × H) 105.4 mm ×...
  • Page 30 CHAPTER 2: OVERVIEW AND SPECIFICATIONS 2–8 EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE...
  • Page 31 Digital Energy Multilin EPM 2200 Multi-function Power Metering System Chapter 3: Mechanical Installation Mechanical Installation Introduction The EPM2200 meter can be installed using a standard ANSI C39.1 (4" Round) or an IEC 92mm DIN (Square) form. In new installations, simply use existing DIN or ANSI punches. For existing panels, pull out old analog meters and replace with the EPM2200 meter.
  • Page 32 CHAPTER 3: MECHANICAL INSTALLATION ANSI Mounting Rods (screw-in) Mounting Brackets FIGURE 3–1: EPM2200 Mounting Information Recommended Tools for EPM2200 Meter Installation: • #2 Phillips screwdriver, small wrench and wire cutters. • Mount the meter in a dry location free from dirt and corrosive substances. The meter is designed to withstand harsh environmental conditions.
  • Page 33 CHAPTER 3: MECHANICAL INSTALLATION ANSI Installation Steps Insert 4 threaded rods by hand into the back of meter. Twist until secure. Slide ANSI 12 Mounting Gasket onto back of meter with rods in place. Slide meter into panel. Secure from back of panel with lock washer and nut on each threaded rod. Use a small wrench to tighten.
  • Page 34: Din Installation Steps

    CHAPTER 3: MECHANICAL INSTALLATION DIN Installation Steps Slide meter with NEMA 12 Mounting Gasket into panel. (Remove ANSI Studs, if in place.) From back of panel, slide 2 DIN Mounting Brackets into grooves in top and bottom of meter housing. Snap into place. Secure meter to panel with lock washer and a #8 screw through each of the 2 mounting brackets.
  • Page 35 Communications terminals. • GE recommends the use of Shorting Blocks and Fuses for voltage leads and power supply to prevent hazardous voltage conditions or damage to CTs, if the meter needs to be removed from service. CT grounding is optional.
  • Page 36: Ct Leads Terminated To Meter

    CHAPTER 4: ELECTRICAL INSTALLATION There is no required preventive maintenance or inspection necessary for safety. Note however, any repair or maintenance should be performed by the factory. DISCONNECT DEVICE: The following part is considered the equipment disconnect device: A switch or circuit-breaker shall be included in the end-use equipment or building installation.
  • Page 37: Ct Leads Pass-Through (No Meter Termination)

    CHAPTER 4: ELECTRICAL INSTALLATION Wiring diagrams are detailed in the diagrams shown below in this chapter. Communications connections are detailed in Chapter 5. 4.1.2 CT Leads Pass-Through (No Meter Termination) The second method allows the CT wires to pass through the CT Inputs without terminating at the meter.
  • Page 38: Voltage And Power Supply Connections

    CHAPTER 4: ELECTRICAL INSTALLATION Crimp CT terminations FIGURE 4–3: Quick Connect Electrical Connection 4.1.4 Voltage and Power Supply Connections Voltage Inputs are connected to the back of the unit via a optional wire connectors. The connectors accommodate up to AWG#12 / 2.5 mm wire. 4–4 EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM –...
  • Page 39: Ground Connections

    4.1.6 Voltage Fuses GE Multilin recommends the use of fuses on each of the sense voltages and on the control power, even though the wiring diagrams in this chapter do not show them. • Use a 0.1 Amp fuse on each voltage input.
  • Page 40: Electrical Connection Diagrams

    CHAPTER 4: ELECTRICAL INSTALLATION Electrical Connection Diagrams 4.2.1 Description Choose the diagram that best suits your application and maintains the CT polarity. Three-phase, four-wire system Wye with no PTs (direct voltage), 3 CTs, 3 element. 1a. Dual Phase Hookup 1b. Single Phase Hookup Three-phase, four-wire system Wye with no PTs (direct voltage), 3 CTs, 2.5 element.
  • Page 41: (1) Wye, 4-Wire With No Pts And 3 Cts, No Pts, 3 Element

    CHAPTER 4: ELECTRICAL INSTALLATION 4.2.2 (1) Wye, 4-Wire with no PTs and 3 CTs, no PTs, 3 Element For this wiring type, select (3-element Wye) in the meter programming setup. 3 EL WYE FIGURE 4–5: 4-Wire Wye with no PTs and 3 CTs, 3 Element EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM –...
  • Page 42: 1A) Dual Phase Hookup

    CHAPTER 4: ELECTRICAL INSTALLATION 4.2.3 (1a) Dual Phase Hookup 4–8 EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE...
  • Page 43: 1B) Single Phase Hookup

    CHAPTER 4: ELECTRICAL INSTALLATION 4.2.4 (1b) Single Phase Hookup EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE 4–9...
  • Page 44: (2) Wye, 4-Wire With No Pts And 3 Cts, 2.5 Element

    CHAPTER 4: ELECTRICAL INSTALLATION 4.2.5 (2) Wye, 4-Wire with no PTs and 3 CTs, 2.5 Element For this wiring type, select (2.5-element Wye) in the meter programming setup. 2.5EL WYE FIGURE 4–6: 4-Wire Wye with no PTs and 3 CTs, 2.5 Element 4–10 EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM –...
  • Page 45: Ct S , 3 Element

    CHAPTER 4: ELECTRICAL INSTALLATION 4.2.6 (3) Wye, 4-Wire with 3 PTs and 3 CTs, 3 Element For this wiring type, select (3-element Wye) in the meter programming setup. 3 EL WYE FIGURE 4–7: 4-Wire Wye with 3 PTs and 3 CTs, 3 Element EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM –...
  • Page 46: Ct S , 2.5 Element

    CHAPTER 4: ELECTRICAL INSTALLATION 4.2.7 (4) Wye, 4-Wire with 2 PTs and 3 CTs, 2.5 Element For this wiring type, select (2.5-element Wye) in the meter programming setup. 2.5EL WYE FIGURE 4–8: 4-Wire Wye with 2 PTs and 3 CTs, 2.5 Element 4–12 EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM –...
  • Page 47: (5) Delta, 3-Wire With No Pts, 2 Cts

    CHAPTER 4: ELECTRICAL INSTALLATION 4.2.8 (5) Delta, 3-Wire with no PTs, 2 CTs For this wiring type, select (2 CT Delta) in the meter programming setup. 2 Ct dEL FIGURE 4–9: 3-Wire Delta with no PTs and 2 CTs EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE 4–13...
  • Page 48: S , 2 Ct S

    CHAPTER 4: ELECTRICAL INSTALLATION 4.2.9 (6) Delta, 3-Wire with 2 PTs, 2 CTs For this wiring type, select (2 CT Delta) in the meter programming setup. 2 Ct dEL FIGURE 4–10: 3-Wire Delta with 2 PTs and 2 CTs 4–14 EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM –...
  • Page 49 CHAPTER 4: ELECTRICAL INSTALLATION 4.2.10 (7) Delta, 3-Wire with 2 PTs, 3 CTs For this wiring type, select (2 CT Delta) in the meter programming setup. 2 Ct dEL FIGURE 4–11: 3-Wire Delta with 2 PTs and 3 CTs EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE 4–15...
  • Page 50: Current -Only Measurement (Three -Phase )

    CHAPTER 4: ELECTRICAL INSTALLATION 4.2.11 (8) Current-Only Measurement (Three-Phase) For this wiring type, select (3 Element Wye) in the meter programming setup. 3 EL WYE FIGURE 4–12: Current-Only Measurement (Three-Phase) Even if the meter is used only for current measurement, the unit requires a AN volts Note reference.
  • Page 51: Current -Only Measurement (Dual -Phase )

    CHAPTER 4: ELECTRICAL INSTALLATION 4.2.12 (9) Current-Only Measurement (Dual-Phase) For this wiring type, select (3 Element Wye) in the meter programming setup. 3 EL WYE FIGURE 4–13: Current-Only Measurement (Dual-Phase) Even if the meter is used only for current measurement, the unit requires a AN volts Note reference.
  • Page 52: Current -Only Measurement (Single -Phase )

    CHAPTER 4: ELECTRICAL INSTALLATION 4.2.13 (10) Current-Only Measurement (Single-Phase) For this wiring type, select (3 Element Wye) in the meter programming setup. 3 EL WYE FIGURE 4–14: Current-Only Measurement (Single-Phase) Even if the meter is used only for current measurement, the unit requires a AN volts Note reference.
  • Page 53: Installation

    The RS485 / KYZ Combo is located on the terminal section of the meter. The EPM2200 meter’s RS485 port can be programmed with the buttons on the face of the meter or by using GE Communicator EXT 3.0 software. The standard RS485 Port Settings are as follows: •...
  • Page 54 CHAPTER 5: COMMUNICATION INSTALLATION FIGURE 5–1: 485P Option with RS-485 Communication Installation RS485 allows you to connect one or multiple EPM2200 meters to a PC or other device, at either a local or remote site. All RS485 connections are viable for up to 4000 feet (1219.20 meters).
  • Page 55 • You may connect up to 31 meters on a single bus using RS485. Before assembling the bus, each meter must be assigned a unique address: refer to Chapter 5 of the GE Communicator EXT User’s Manual for instructions. •...
  • Page 56 CHAPTER 5: COMMUNICATION INSTALLATION FIGURE 5–4: RS485 Daisy Chain Connection FIGURE 5–5: Incorrect “T” and “Star” Topologies 5–4 EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE...
  • Page 57: Epm2200 Communication And Programming Overview

    Software programming and communication utilize the RS485 connection on the back of the meter, as shown in fig 5-3. Once a connection is established, GE Communicator EXT 3.0 software can be used both to program the meter and to communicate with EPM2200 slave devices.
  • Page 58 Connect button. The Device Status screen appears, confirming a connection. FIGURE 5–8: Device Status screen Click OK. The main screen of GE Communicator EXT software reappears. 5–6 EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE...
  • Page 59 CHAPTER 5: COMMUNICATION INSTALLATION Click the Profile icon on the left of the toolbar. A set of EPM2200 Profile Programming Screens appears: Click the Communication tab. The Communication Settings appear. Use drop-down menus to change settings, if desired. EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE 5–7...
  • Page 60: Additional Epm2200 Profile Settings

    CHAPTER 5: COMMUNICATION INSTALLATION Communication Settings • COM2 (RS485) • Address (1-247) • Protocol (Modbus RTU, ASCII) • Baud Rate (9600 to 57600) • Response Delay (0-750 msec) COM1 is not used by the EPM2200 meter. Note When changes are complete, click the Update button to send a new profile to the meter.
  • Page 61 CHAPTER 5: COMMUNICATION INSTALLATION • PT Denominator (Secondary): • PT Multiplier: • PT Fullscale: Calculation Based on Selections System Wiring: Number of Phases: One, Two or Three VOLTS FULL SCALE = PT Numerator x PT Multiplier Note You must specify Primary and Secondary Voltage in Full Scale. Do not use ratios! The PT Denominator should be the Secondary Voltage level.
  • Page 62 CHAPTER 5: COMMUNICATION INSTALLATION ENERGY AND DISPLAY POWER AND ENERGY FORMAT Power Scale Energy Digits Energy Decimal Places Energy Scale (Example Based on Selections) Power Direction: View as Load Demand Averaging Averaging Method: Block or Rolling Interval (Minutes) Sub Interval Auto Scroll: Click to Activate Display Configuration: Click Values to be displayed.
  • Page 63 Enable Password for Reset Enable Password for Configuration Change Password Change VSwitch (Call GE Multilin for Update Information.) Change Device Designation Enter a new Device label in the entry field. Click Update to send a new Profile. After programming the Device Profile, click: •...
  • Page 64 Use GE Communicator EXT to communicate with the device and perform required tasks.Refer to the GE Communicator EXT User’s Manual for more details. You can access the manual online by clicking Help > Contents from the GE Communicator EXT Main screen.
  • Page 65: 6: Using The Meter

    Digital Energy Multilin EPM 2200 Multi-function Power Metering System Chapter 6: Using the Meter Using the Meter Introduction The EPM2200 meter can be configured and a variety of functions can be accomplished simply by using the Elements and the Buttons on the meter face. This chapter will review Front Panel Navigation.
  • Page 66: Meter Face Buttons

    CHAPTER 6: USING THE METER • % of Load Bar: Graphic Display of Amps as % of the Load • Parameter Designator: Indicates Reading Displayed • Scale Selector: Kilo or Mega multiplier of Displayed Readings ENTER MENU button button RIGHT DOWN button button...
  • Page 67 CHAPTER 6: USING THE METER Settings Mode - On, Off, Settings Config Mode - Password Digits, Available Values, Digits Down Button: Scroll DOWN through Mode menus Use Buttons in Modes of Operation: • Operating Mode (default): View Parameter Values • Reset Mode: Reset Stored Max and Min Values •...
  • Page 68: Of Load Bar

    CHAPTER 6: USING THE METER % of Load Bar The 10-segment LED bargraph at the bottom of the EPM2200 unit’s display provides a graphic representation of Amps. The segments light according to the load in the %Load Segment Table below. When the Load is over 120% of Full Load, all segments flash “On”...
  • Page 69: Watt-Hour Accuracy Testing (Verification)

    CHAPTER 6: USING THE METER Watt-hour Accuracy Testing (Verification) To be certified for revenue metering, power providers and utility companies have to verify that the billing energy meter will perform to the stated accuracy. To confirm the meter's performance and calibration, power providers use field test standards to ensure that the unit's energy measurements are correct.
  • Page 70: Infrared & Kyz Pulse Constants For Accuracy Testing

    CHAPTER 6: USING THE METER 6.3.1 Infrared & KYZ Pulse Constants for Accuracy Testing Table 6–2: Infrared & KYZ Pulse Constants for Accuracy Testing Voltage Level Class 10 Models Class 2 Models Below 150 V 0.2505759630 0.0501151926 Above 150 V 1.0023038521 0.2004607704 •...
  • Page 71 Digital Energy Multilin EPM 2200 Multi-function Power Metering System Chapter 7: Configuring the Meter Using the Front Panel Configuring the Meter Using the Front Panel Overview The EPM2200 front panel can be used to configure the meter. The EPM2200 has three MODES: •...
  • Page 72 In this chapter, a typical set up will be demonstrated. Other settings are possible. The complete Navigation Map for the Display Modes is in Appendix A of this manual. The meter can also be configured with software (see GE Communicator EXT 3.0 Manual). 7–2...
  • Page 73 CHAPTER 7: CONFIGURING THE METER USING THE FRONT PANEL Start Up Upon Power Up, the meter will display a sequence of screens. The sequence includes the following screens: • Lamp Test Screen where all LEDs are lighted • Lamp Test Screen where all digits are lighted •...
  • Page 74: Main Menu

    CHAPTER 7: CONFIGURING THE METER USING THE FRONT PANEL Configuration 7.3.1 Main Menu Push MENU from any of the Auto-Scrolling Readings. The MAIN MENU Screens appear. The String for Reset Mode (rSt) appears (blinking) in the A Screen. If you push DOWN, the MENU scrolls and the String for Configuration Mode (CFG) appears (blinking) in the A Screen.
  • Page 75 CHAPTER 7: CONFIGURING THE METER USING THE FRONT PANEL • If you push the RIGHT button, the RESET All? YES screen appears. • To Reset All, you must enter a 4-digit Password, if Enabled in the software (see section 5.2.2). •...
  • Page 76: Configuration Mode

    CHAPTER 7: CONFIGURING THE METER USING THE FRONT PANEL • If an incorrect Password has been entered, “PASS ---- FAIL” appears and the screen returns to Reset ALL? YES. 7.3.3 Configuration Mode The following procedure describes how to navigate the configuration mode menu. Press the MENU Button from any of the auto-scrolling readings.
  • Page 77: Configuring The Scroll Feature

    CHAPTER 7: CONFIGURING THE METER USING THE FRONT PANEL Push the DOWN Button to scroll all the parameters: scroll, CT, PT, connection ) and port. Cnct The active parameter is always flashing and displayed in the “A” screen. 7.3.4 Configuring the Scroll Feature Use the following procedure to configure the scroll feature.
  • Page 78 CHAPTER 7: CONFIGURING THE METER USING THE FRONT PANEL Once the correct password is entered, push ENTER. message will reappear, the PRG faceplate LED will flash, and the first Ct-n digit of the “B” screen will also flash. Use the DOWN button to change the first digit. Use the RIGHT button to select and change the successive digits.
  • Page 79: Configuring The Ct Setting

    CHAPTER 7: CONFIGURING THE METER USING THE FRONT PANEL 7.3.6 Configuring the CT Setting Use the following procedure to program the CT setting. Push the DOWN Button to scroll through the configuration mode parameters. Press ENTER when is the active parameter (i.e. it is in the “A” screen and flashing). This will display the and the (CT numerator) screen.
  • Page 80: Configuring The Pt Setting

    CHAPTER 7: CONFIGURING THE METER USING THE FRONT PANEL Example settings for the value are shown below: Ct-S 200/5 A: set the value for “200” and the value for “1” Ct-n Ct-S 800/5 A: set the value for “800” and the value for “1”...
  • Page 81: Configuring The Connection (Cnct) Setting

    CHAPTER 7: CONFIGURING THE METER USING THE FRONT PANEL value can be “1”, “10”, or “100”. Refer to Programming the Configuration Mode Pt-S Screens on page 7–7 for instructions on changing values. Example settings for the , and values are shown below: Pt-n Pt-d Pt-S...
  • Page 82: Configuring The Communication Port Setting

    CHAPTER 7: CONFIGURING THE METER USING THE FRONT PANEL 3-Element Wye 2.5-Element Wye 2 CT Delta Press ENTER to scroll through the other parameters. Press DOWN or RIGHT to display the Password screen (see Reset Mode above for details). Press MENU to return to the main Configuration menu. 7.3.9 Configuring the Communication Port Setting Use the following procedure to program the communication port (...
  • Page 83 CHAPTER 7: CONFIGURING THE METER USING THE FRONT PANEL Address 005 Refer to Programming the Configuration Mode Screens above for details on changing values. • The next screen is the baud rate ( ). The current baud rate is displayed POrt bAUd on the “B”...
  • Page 84: 7.3.10 Operating Mode

    CHAPTER 7: CONFIGURING THE METER USING THE FRONT PANEL Refer to Programming the Configuration Mode Screens above for details on changing values. The three protocol selections are shown below. Press ENTER to scroll through the other parameters. Press DOWN or RIGHT to display the Password screen (see Reset Mode on page 7–4 for details).
  • Page 85: Appendix A: Epm2200 Navigation Maps

    • An Overview of Programming using the buttons can be found in Chapter 7. • The meter can also be programmed using software (see GE Communicator EXT 3.0 Manual). EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE APPENDIX A–1...
  • Page 86: Epm2200 Navigation Map Titles

    APPENDIX A: EPM2200 NAVIGATION MAPS Appendix A.2 Navigation Maps (Sheets 1 to 4) The EPM2200 Navigation Maps begin on the next page. They show in detail how to move from one screen to another and from one Display Mode to another using the buttons on the face of the meter. All Display Modes will automatically return to Operating Mode after 10 minutes with no user activity.
  • Page 87 APPENDIX A: EPM2200 NAVIGATION MAPS EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE APPENDIX A–3...
  • Page 88 APPENDIX A: EPM2200 NAVIGATION MAPS APPENDIX A–4 EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE...
  • Page 89 APPENDIX A: EPM2200 NAVIGATION MAPS EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE APPENDIX A–5...
  • Page 90 APPENDIX A: EPM2200 NAVIGATION MAPS APPENDIX A–6 EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE...
  • Page 91: Appendix B: Modbus Mapping For Epm2200

    (Chapter 7). The meter can also be programmed using software. For a Programming Overview, see section 5.2 of this manual. For further details see the GE Communicator EXT 3.0 Manual. EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE...
  • Page 92 APPENDIX B: MODBUS MAPPING FOR EPM2200 Appendix B.2 Modbus Register Map Sections The EPM2200 Modbus Register Map includes the following sections: Fixed Data Section, Registers 1- 47, details the Meter’s Fixed Information described in Section 7.2. Meter Data Section, Registers 1000 - 5003, details the Meter’s Readings, including Primary Readings, Energy Block, Demand Block, Maximum and Minimum Blocks, THD Block, Phase Angle Block and Status Block.
  • Page 93 APPENDIX B: MODBUS MAPPING FOR EPM2200 Appendix B.3 Data Formats ASCII: ASCII characters packed 2 per register in high, low order and without any termination charcters. Example: “EPM2200” would be 4 registers containing 0x5378, 0x6172, 0x6B31, 0x3030. SINT16/UINT16:16-bit signed/unsigned integer. SINT32/UINT32:32-bit signed/unsigned integer spanning 2 registers.
  • Page 94: Floating Point Values

    APPENDIX B: MODBUS MAPPING FOR EPM2200 Appendix B.4 Floating Point Values Floating Point Values are represented in the following format: Register Byte Meaning m m m m m m m m m m m m m m m m m m m m m m m sign exponent mantissa...
  • Page 95: Modbus Register Map

    APPENDIX B: MODBUS MAPPING FOR EPM2200 Appendix B.5 Modbus Register Map Table Appendix B –1: Modbus Register Map (Sheet 1 of 7) Units or Decimal Format Comments Description Range Resolution Fixed Data Section Identification Block read-only 0000 - 0007 1 Meter Name ASCII 16 char...
  • Page 96 APPENDIX B: MODBUS MAPPING FOR EPM2200 Table Appendix B –1: Modbus Register Map (Sheet 2 of 7) Units or Decimal Format Comments Description Range Resolution Primary Energy Block read-only 044B - 044C 1100 - 1101 W-hours, Received SINT32 0 to 99999999 or Wh per energy * Wh received &...
  • Page 97 APPENDIX B: MODBUS MAPPING FOR EPM2200 Table Appendix B –1: Modbus Register Map (Sheet 3 of 7) Units or Decimal Format Comments Description Range Resolution 0BCF - 0BD0 3024 - 3025 Negative VARs, 3-Ph, FLOAT 0 to +9999 M VARs Minimum Avg Demand 0BD1 - 0BD2 3026 - 3027 VAs, 3-Ph, Minimum FLOAT...
  • Page 98 APPENDIX B: MODBUS MAPPING FOR EPM2200 Table Appendix B –1: Modbus Register Map (Sheet 4 of 7) Units or Decimal Format Comments Description Range Resolution Status Block read-only 1387 - 1387 5000 - 5000 Meter Status UINT16 bit-mapped --exnpch exnpch = EEPROM block ssssssss OK flags (e=energy, x=max, n=min,...
  • Page 99 APPENDIX B: MODBUS MAPPING FOR EPM2200 Table Appendix B –1: Modbus Register Map (Sheet 5 of 7) Units or Decimal Format Comments Description Range Resolution Programmable Settings Section (See note 15) Basic Setups Block write only in PS update mode 752F - 752F 30000 - 30000 CT multiplier &...
  • Page 100 APPENDIX B: MODBUS MAPPING FOR EPM2200 Table Appendix B –1: Modbus Register Map (Sheet 6 of 7) Units or Decimal Format Comments Description Range Resolution 7549 - 7549 30026 - 30026 COM2 setup UINT16 bit-mapped ----dddd -ppp- dddd = reply delay (* 50 msec) ppp = protocol (1-Modbus RTU, 2-Modbus ASCII)
  • Page 101 APPENDIX B: MODBUS MAPPING FOR EPM2200 Table Appendix B –1: Modbus Register Map (Sheet 7 of 7) Units or Decimal Format Comments Description Range Resolution 9C4B - 9C4B 40012 - 40012 Frequency UINT16 0 to 2730 0= 45 or less, 2047= 60, 2730= 65 or more freq = 45 + ((register / 4095) * 30)
  • Page 102 APPENDIX B: MODBUS MAPPING FOR EPM2200 M denotes a 1,000,000 multiplier. Not applicable to EPM2200 Writing this register causes data to be saved permanently in EEPROM. If there is an error while saving, a slave device failure exception is returned and programmable settings mode automatically terminates via reset.

This manual is also suitable for:

Pl2200-b-s